Welcome Customer !

Membership

XwbooElectronic ComponentsPiezoelectric Crystal, Frequency ElementTransducerS3-PD POWER FACTOR TRANSDUCER
  • $item.Title
  • $item.Title

S3-PD POWER FACTOR TRANSDUCER

Haiyan Jinhan Electronics Technology Co., Ltd.

Model
Nature of the Manufacturer
Other
Product Category
Transducer
Place of Origin
,
S3-PD-1 1φ2W,Class: 0.2%RO; N3-PD-1 1φ2W, Class: 0.5%ROS3-PD-3 3φ3W, Class: 0.2%RO; N3-PD-3 3φ3W, Class: 0.5%ROS3-PD-3A 3φ4W, Class: 0.2%RO; N3-PD-3A 3φ4W, Class: 0.5%RO

1.EATURES

◆Excellent long term stability (4 ~ 20mA, 500W)

◆Precision measurement even for distorted wave

◆High impulse & surge protection (5KV)

◆The case can be mounted on a 35mm rail which complies with DIN 46277

2.DESCRIPTION

◆Model:

S3-PD-1 :1φ2W,Class: 0.2%RO;
N3-PD-1 :1φ2W, Class: 0.5%RO
S3-PD-3 :3φ3W, Class: 0.2%RO;
N3-PD-3 :3φ3W, Class: 0.5%RO
S3-PD-3A:3φ4W, Class: 0.2%RO;
N3-PD-3A : 3φ4W, Class: 0.5%RO

These transducers require an auxiliary power supply and offer a highly accurate method of measuring the phase angle of the input. They have a full four quadrant capability. The output is a linear function of the phase angle between the two inputs (which can be current or voltage), the circuit can also be used as power factor transducer only added a COS circuit.

Output amplifier provides constant voltage or current output. Output is unaffected by load resistance provided it is within the specified range.

3.SPECIFICATION

3.1 INPUT

Input Range

Max. Input Over Capability

Circuit

Amp.

Voltage

Range

Single Phase

5 A

110V (120V)

(Lead) (Lag) 0.5 ~ 1 ~ 0.5

or (Lead) (Lag) 60 ~ 0 ~ 60

Ampere:

3 x rated continuous 10 x rated 10 sec.

50 x rated 1 sec.

Voltage:

2 x rated continuous

220V (240V)

3-Phase 3-Wire

5 A

110V (120V)

220V (240V)

3-Phase 4-Wire

5 A

190V/110V (208/120V)

380V/220V (416/240V)


3.2 OUTPUT

DC Output Range

Load Resistance

Output Resistance

Output Ripple

Response Time

-1 ~ 0 ~ 1V

1KW

<-0.05W

<- 0.5% RO.

(Peak)

<-400mS. 0 ~ 99%

-5 ~ 0 ~ 5V

1 ~ 3 ~ 5V

0 ~ 5 ~ 10V

-1 ~ 0 ~ 1mA

0 ~ 10KW

20MW

-10 ~ 0 ~ 10mA

0 ~ 1KW

5MW

0 ~ 10 ~ 20mA

0 ~ 500 W

4 ~ 12 ~ 20mA

Aux. power supply

AC 110V ± 15%, 50/60HZ

AC 220V ± 15%, 50/60HZ

DC24V, 48V, 110V, ± 15%

Power consumption

-2.5VA, ≤DC 3W

Power effect

≤0.1% RO

Waveform effect

≤0.2% RO. at distortion factor 30%( PCIR)

Output load effect

≤0.05% RO.

Magnetic field strength

-0.2% RO., 400A/M

Span adjustment range

5%RO

Zero adjustment range

1%RO

Operating temperature range

0 ~ 60℃

Operating temperature range

0 ~ 60℃

Storage temperature range

-10 ~ 70℃

Temperature coefficient

- 100PPM from 0 to 60℃

≤ 60PPM, 25。C ± 10℃

Max. relative humidity

95%

Isolation

Input/output/power/case

Insulation resistance

100M W, DC 500V

Dielectric withstand voltage

Between input/output/power/case

(IEC 414, 688,ANSI, C37) AC 2.6KV, 60HZ, 1 min.

Impulse withstand test

5KV, 1.2 X 50μS

(IEC 255-4, ANSI C37 90a) Common mode & differential mod

Performance

Designed to comply with IEC688

Safety requirements

IEC 414, BS5458

4.Trminal Connection:
4.1 S3-PD-1, N3-PD-1 (1φ2W):

5.2 S3-WD-3, N3-WD-3 (3φ3W)

5.3 S3-PD-3A, N3-PD-3A (3φ4W)


6.THE OUTSIDE DIMENSION (UNIT:mm)

7.PANEL MOUNTING HOLES (UNIT:mm)



1. Model:

S3-PD-1 : 1φ2W,Class: 0.2%RO;
S3-PD-3 : 3φ3W, Class: 0.2%RO;
S3-PD-3A : 3φ4W, Class: 0.2%RO;
N3-PD-1 : 1φ2W, Class: 0.5%RO
N3-PD-3 : 3φ3W, Class: 0.5%RO
N3-PD-3A :3φ4W, Class: 0.5%RO

2.Order form:


2. Example of model and parameter filling:

(1) S3-PD-3-555A4B

0.5%RO, 3φ3W power factor transducer

Input nominal current: 5A;

Input nominal voltage: 100V;

Input signal frequency: 50±5Hz;

Output range: 4~12~20mA;

Correspond to -0.5 (capacity) ~1~0.5 (inductive);

Auxiliary power supply: AC220V.

(2) S3-PD-3A-165A5B

0.5%RO, 3φ3W system power factor transducer

Input nominal current: 1A;

Input nominal voltage: 57.7V;

Input signal frequency: 50±5Hz;

Output range: -20~0~20mA;

Correspond to -0.5 (capacity) ~1~0.5 (inductive);

Auxiliary power supply: AC220V.

Note:

1 If the user needs other special calibration, please indicate the parameter value in the contract.

2 power factor input, output value conversion:

y = a1cosф+b1(ф:0 to 60°)

y = a2cosф+b2(ф:0~-60°)

In the above formula: y is the output of the power factor transducer, and y, a, b should be selected according to the different output modes of the powe


Haiyan Jinhan Electronics Technology Co., Ltd was founded on November 18, 2004 which located in Haiyan Science and Technology Park, NO 211, Yanbei Road, Zhejiang China.Our goal is to design and manufacture multiple series of products for power systems. With the ISO9001 / ISO9002 approvals, we have always sustained the principle of producing the best quality, best service and best technical skills.For over 10 years, JINHANCN has contributed and always strived to develop the most durable and stable products for the usage of power systems. We have earned excellent customer feedback and marketing reputation from all over the world.Our products have been applied to both measuring instruments and power distribution systems for utilities and related industries. And we also have developed various series of products to meet the demands of various marketing such as FP/GP/EP/S3/N3 Series High-reliability Power Transmitter, Transmission Screen, Malfunctional Electric Energy Meter, Temperature Controller etc.We truly believe that to give our customers the best service is our main purpose and long-term responsibility.With spirited teamwork, our business has expanded to global markets successfully. All JINHANCN products are originally designed and manufactured (ODM).We have been researching and developing new high-tech products continually in order to meet increasing demand for electricity. To improve business administration and quality assurance, we run CWQC (company wide quality control) with strict step by step quality compliance to our production procedure in compliance with ISO9001.
Similar Product Recommend