Membership
Help
Haiyan Jinhan Electronics Technology Co., Ltd.
Haiyan Jinhan Electronics Technology Co., Ltd.
1.FEATURES
◆Excellent long term stability (4 ~ 20mA, 500 W )
◆Precision measurement even for unbalance system
◆Precision measurement even for distorted wave
◆High impulse & surge protection (5KV)
◆The case can be mounted on a 35mm rail which complies with DIN 46277.
2.DESCRIPTION
Input Range | Max. Input Over Capability | |||
Circuit | Amp. | Voltage | Basic W | |
Single Phase | 5 A | 110V (120V) | ± 0.5KW | Ampere: 3 x rated continuous 10 x rated 10 sec. 50 x rated 1 sec.
Voltage: 2 x rated continuous |
220V (240V) | ± 1KW | |||
3-Phase 3-Wire |
5 A | 110V (120V) | ± 1KW | |
220V (240V) | ± 2KW | |||
3-Phase 4-Wire | 5 A | 190V/110V (208/120V) | ± 1.5KW | |
380V/220V (416/240V) | ± 3KW | |||
◆OUTPUT:
DC Output Range | Load Resistance | Output Resistance | Output Ripple | Response Time |
-1 ~ 0 ~ 1V | 1K | ≤0.05W | ≤ 0.5% RO. (Peak) | ≤400mS. 0 ~ 99% |
-5 ~ 0 ~ 5V | ||||
1 ~ 3 ~ 5V | ||||
0 ~ 5 ~ 10V | ||||
-1 ~ 0 ~ 1mA | 0 ~ 10K | 20MW | ||
-10 ~ 0 ~ 10mA | 0 ~ 1K |
5MW | ||
0 ~10 ~ 20mA | 0~500 W | |||
4 ~12 ~ 20mA |
4.Specification:
Aux. power supply | AC 110V ± 15%, 50/60HZ AC 220V ± 15%, 50/60HZ DC24V, 48V, 110V, ± 15% |
Power consumption | -2.5VA, ≤DC 3W |
Power effect | ≤0.1% RO |
Waveform effect | ≤0.2% RO. at distortion factor 30%( PCIR) |
Output load effect | ≤0.05% RO. |
Magnetic field strength | -0.2% RO., 400A/M |
Span adjustment range | 5%RO |
Zero adjustment range | 1%RO |
Operating temperature range | 0 ~ 60℃ |
Operating temperature range | 0 ~ 60℃ |
Storage temperature range | -10 ~ 70℃ |
Temperature coefficient | - 100PPM from 0 to 60℃ ≤ 60PPM, 25。C ± 10℃ |
Max. relative humidity | 95% |
Isolation | Input/output/power/case |
Insulation resistance | 100M W, DC 500V |
Dielectric withstand voltage | Between input/output/power/case (IEC 414, 688,ANSI, C37) AC 2.6KV, 60HZ, 1 min. |
Impulse withstand test | 5KV, 1.2 X 50μS (IEC 255-4, ANSI C37 90a) Common mode & differential mod |
Performance | Designed to comply with IEC688 |
Safety requirements | IEC 414, BS5458 |




1. Model:
S3-WD-1: 1φ2W active power transducer, accuracy : 0.2% RO
S3-WD-1S : 1φ2W active power transducer, accuracy : 0.2% RO, (dual output)
S3-WD-3: 3φ3W active power transducer, accuracy : 0.2% RO
S3-WD-3S : 3φ3W active power transducer, accuracy : 0.2% RO (dual output)
S3-WD-3A: 3φ4W active power transducer, accuracy : 0.2% RO
S3-WD-3AS: 3φ4W active power transducer, accuracy : 0.2% RO (dual output)
N3-WD-1: 1φ2W active power transducer, accuracy : 0.5% RO
N3-WD-1S : 1φ2W active power transducer, accuracy : 0.5% RO, (dual output)
N3-WD-3: 3φ3W active power transducer, accuracy : 0.5% RO
N3-WD-3S : 3φ3W active power transducer, accuracy : 0.5% RO (dual output)
N3-WD-3A: 3φ4W active power transducer, accuracy : 0.5% RO
N3-WD-3AS: 3φ4W active power transducer, accuracy : 0.5% RO (dual output)
2.Order form:

3. Example of model and parameter filling:
(1) N3-WD-3-555A4BY
0.5%RO, 3φ3W active power transducer
Input nominal current: 5A; input nominal voltage: 100V;
Nominal input power 2: 866W;
Input signal frequency: 50±5Hz;
Output range: 4~12~20mA;
Correspondence -866~0~866W
Auxiliary power supply: AC220V.
Need to measure the reverse power.
(2) S3-WD-3-155A3BN
0.2%RO, 3φ3W active power transducer
Input nominal current: 1A;
input nominal voltage: 100V;
Nominal input power 2:170W;
Input signal frequency: 50±5Hz;
Output range: 0~20mA;
Corresponding 0~170W
Auxiliary power supply: AC220V.
There is no need to measure reverse power.
(3) S3-WD-3A-525V5BY
0.2%RO, 3φ4W active power transducer
Input nominal current: 5A;
input nominal voltage: 220V;
Nominal input power 2: 3300W;
Input signal frequency: 50±5Hz;
Output range: -10~0~10V;
Correspondence -3300~0~3300W
Auxiliary power supply: AC220V.
Need to measure the reverse power.
Note:
1 The value in the output range () is the value specified for positive and reverse power output.
2 system power calibration:
Single phase is the input nominal voltage × input nominal current;
The three-phase three-wire system is double the input nominal voltage × input nominal current;
Three-phase four-wire system is 3 times the input nominal voltage × input nominal current;
Calibration of non-nominal power: usually keep the input voltage at the nominal value,
The required power rating is obtained by changing the input current.
The output of the 3 dual output is 1 (+) and 2 (-) terminals.
4 If the user needs other special calibration, please indicate the parameter value in the contract.