Structure
The enclosure is a perfect sealing system,at the rear of this gas tank, there is a valve for pressure relief when the arc fault leads to the overpressure of SF6 gas.
Operation mechanism
Using spring operating mechanisms:
There are single spring and double spring -2 types of mechanisms for your choice.
Both types could become motorized by mounting a motor part.
Main technical specifications
| Item NO. | Name | Unit | Technical parameters | |||
| Load break switch panel | ||||||
| 1 | Rated Voltage Un | kV | 12 | 24 | 36 | |
| 2 | Rated Frequency | Hz | 50 | 50 | 50 | |
| 3 | Rated Current | A | 630 | 630 | 630 | |
| 4 | Rated Load Breaking Current | A | 630 | 630 | 630 | |
| 5 | Rated Short Time Withstand Current(rms) | kA | 20 | 20 | 20 | |
| 6 | Rated Short Time Duration | s | 3 | 3 | 3 | |
| 7 | Rated Peak Withstand Current | kA | 50 | 50 | 50 | |
| 8 | Rated Closed Switch - Off Current | A | 630 | 630 | 630 | |
| 9 | Rated Cable Charging Breaking Current | A | 10 | 10 | 10 | |
| 10 | Rated Active Load Breaking Current | A | 630 | 630 | 630 | |
| 13 | Earthing Switch 2s Short Time Withstand Current | kA | 20 | 20 | 20 | |
| 14 | Rated Short-Circuit Current Making Times | times | 2 | 2 | 2 | |
| 15 | Rated Current Breaking Times | times | 10 | 10 | 10 | |
| 16 | Mechanical Endurance | Load Break Switch | times | 3000 | 3000 | 3000 |
| Earthing Switch | times | 2000 | 2000 | 2000 | ||
| 17 | SF6 gas anual leakage rate≤ | /year | 0.10% | 0.10% | 0.10% | |
| 18 | Rated Insulation Level | Unit | Technical parameters | |||
| 1min Power Frequency withstand voltage(rms) | On isolating distance | kV | 48 | 60 | 110 | |
| Phase to Phase | kV | 42 | 50 | 85 | ||
| Phase to Earth | kV | 42 | 50 | 85 | ||
| Lightning impulse withstand voltage(peak) | On isolating distance | kV | 85 | 145 | 215 | |
| Phase to Phase | kV | 75 | 125 | 185 | ||
| Phase to Earth | kV | 75 | 125 | 185 | ||
Note: For short circuit breaking and peak current is based on Fuse plus combination.

FAQ
1. How long is the warranty period?
Normally 12 months warranty period.
1. What payment term do you accept?
T/T,west union and others upon request.
4.How to place order?
Please send us your detailed requirements and we
3.How about type test?
Our client passed type test in Europe, and we also type tested in China.