Membership
Help
Zhejiang Volcano electrical technology Co., Ltd
Zhejiang Volcano electrical technology Co., Ltd

PRODUCT INTRODUCTION
The JDZ11-24 voltage transformer is a fully enclosed epoxy resin casting indoor product, which is suitable for voltage and electric energy measurement and relay protection in power systems with rated frequency of 50Hz and rated voltage of 24kV.The product is small in volume, light in weight, only occupying limited space for installation, compact in overall structure and convenient in use.
This type of voltage transformer is of totally enclosed structure. It adopts epoxy resin fully enclosed casting. The iron core is wound into a ring by high-quality cold-rolled silicon steel. The primary and secondary windings are wound on the iron core. The product has good resistance to pollution and moisture. It can also be installed at any position and in any direction. The secondary outlet terminal has a terminal box, which has three different outlet directions. The wiring is very convenient and the anti stealing measures can be realized.
SERVICE CONDITIONS
(1) altitude: not more than 3000m;
(2) humidity: ≤ 85%;
(3) ambient temperature: - 5 ℃ ~ + 40 ℃;
(4) creepage distance: meet class II pollution level;
(5) there is no gas, steam, chemical deposition and other explosive and corrosive
media that seriously affect the insulation of transformer in the installation site.
TECHNICAL DATA
Model | Rated transformation ratio(kV) | Accuracy classes combination | Rated output (VA) | Thermal limit output (VA) | Rated insulation level (kV) |
JDZX11-15 | 13.8/√3/0.1/√3/0.1/3 | 0.2/6P(3P) 0.5/6P(3P) 1/6P(3P) | 30/100 80/100 150/100 | 400 | 18/55/105 |
15/√3/0.1/√3/0.1/3 | |||||
15.7/√3/0.1/√3/0.1/3 | |||||
18/√3/0.1/√3/0.1/3 | |||||
JDZX11-20 | 20/√3/0.1/√3/0.1/3 | 24/65/125 | |||
JDZX11-15 | 13.8√3/0.1/√3/0.1/√3/0.1/3 | 0.2/0.2/6P(3P) 0.2/0.5/6P(3P) 0.2/0.5/6P(3P) | 15/15/100 20/20/100 30/30/100 | 300 | 18/55/105 |
15/√3/0.1/√3/0.1/√3/0.1/3 | |||||
15.7/√3/0.1/√3/0.1/√3/0.1/3 | |||||
18/√3/0.1/√3/0.1/√3/0.1/3 | |||||
JDZX11-20 | 20/√3/0.1/√3/0.1/√3/0.1/3 | 24/65/125 |
Notes:
1.When in use, the secondary winding shall not be short-circuited and overload operation.
2.JDZX 11-20 is semi-insulated structure, which can only be used for induction withstand voltage test.
3.The transformer should be disconnected from the switchgear when the magnetic switch cabinet is tested on power frequency.
