| Order Data | Order No. |
| PROFIBUS-DP Slave Station Modules, Communication rate 12M, Isolation. | CTH2 277-0AA32 |
| PROFIBUS-DP Slave Station Modules, Communication rate 1.5M, Isolation. | CTH2 277-0AB32 |
Performance Parameters
Features | |||||
Order No. | CTH2 277-0AA32 | ||||
Dimension(W×H×D) | 71.3× 96 × 62mm | ||||
Port number | 1 | ||||
Electrical interface | Isolated RS485 | ||||
I/O | 0 | ||||
Maximum extension module number | 6 | ||||
PROFIBUS-DP/MPI baud rate(auto setting) | 9.6、19.2、45.45、93.75、187.5 and 500Kbps;1、1.5、3.6 and 12Mbps | ||||
Protocol | PROFIBUS-DP slave device and MPI slave device | ||||
LED | OFF | Red | Red indicator blink | Green | |
DX MODE | not on data exchange mode | -- | -- | on data exchange mode | |
DP ERROR | no fault | not on data exchange mode | parametric/configuration errors | -- | |
POWER | no power | -- | -- | normal | |
CPU FAULT | good | Module fault | -- | -- | |
Maximum cable length | |||||
Less than 93.75Kbps baud rate | 1200m | ||||
187.5Kbps baud rate | 1000m | ||||
500Kbps baud rate | 400m | ||||
1 ~ 1.5Mbps baud rate | 200m | ||||
3 ~ 12Mbps baud rate | 100m | ||||
Network performance | |||||
Station address setting | 0~126(setting by dial switch ) | ||||
Max station number per group | 32 | ||||
Max station number per network | 126、up to 125 SM277 stations | ||||
MPI connect | Total 6 ,2 reservation(1 for PG,1 for OP) | ||||
24VDC power supply input | |||||
Power range | 20.4 ~ 28.8VDC(2 category or PLC sensor power supply ) | ||||
Power supply | 2.3W | ||||
Max current(activate the communication port) | 70mA | ||||
Ripple noise(<10Mhz) | <1V peak to peak value(max.) | ||||
Features | ||
Order No. | CTH2 277-0AB32 | |
Dimension(W×H×D) | 71.3 × 96 × 62mm | |
Port number | 1 | |
Electrical interface | Isolated RS485(500VAC) | |
PROFIBUS-DP baud rate(auto setting) | 9.6、19.2、45.45、93.75、187.5 and 500Kbps;1、1.5Mbps | |
Protocol | PROFIBUS-DP V0 slave device | |
IO | - | |
Expansion IO | ||
Max expansion module | 6 | |
Max smart module | - | |
Max I/O(mapping) | 256(128 In/128 Out) | |
LED indicator | ||
ON(green) | light up when power on | |
SF(red) | If SM 277B check out error,or expansion IO module fault,indicator blink。 | |
BF(red) | when do not DP exchange with master station,indicator blink。 | |
Maximum cable length | ||
No more than 93.75Kbps baud rate | 1200m | |
187.5Kbps baud rate | 1000m | |
500Kbps baud rate | 400m | |
1 ~ 1.5Mbps | 200m | |
Network performance | ||
Station address setting | 0~126(setting by dial switch) | |
Max station number per group | 32 | |
Max station number per network | 126,up to 125 SM277B station | |
24VDC power supply input | ||
Power range | 20.4~28.8VDC(2 category or PLC sensor power supply ) | |
Isolation | - | |
Power supply | 8W | |
Current output for sensor(24VDC) | ||
Power range | 20.4~28.8VDC(2 category or PLC sensor power supply) | |
24V max current output | 400mA | |
Current output for expansion module(5VDC) | ||
5V max current output | 660mA | |
Size Diagram