Membership
Help
YUEQING MEANRAY ELECTRIC CO., LTD.
YUEQING MEANRAY ELECTRIC CO., LTD.
DC SURGE PROTECTIVE DEVICE
MR2-600PV
Brand Name: MEANRAY
Place of Origin: Zhejiang, China
Model Number: MR-PV600
Color: RED
Type: MR2-PV600
Electricity Type: DC
MR-PV series for installation of the DC side to protect the terminal device in a PV system, like solar panels and inverters against the effects of lightning surge current.
Red=Replace, Visual Indication: Green=OK,
Features:
a.Small creepage current,fast response time, remnant low voltage
b.With remote connection, can realize remote contro
c.Module design, convenient installation,with easy electric maintains operation
d.Built-in over current and over heat, temperature control open circuit technology
e.Adopt independent intelligence property right and high performance sensitivity resistance plates
SPECITICATIONO
| MR2-PV series surge protector | MR2-PV | |||
PV DC-specific(IEC66143-1/EN61643-31) | 2P | 2P | 2P | |
Pole | ||||
Electrical parameter | ||||
Classified test | Ⅱ | Ⅱ | Ⅱ | |
UCPV(VDC) | 500 | 600 | 800 | |
In(8/20)us (kA) | 20 | 20 | 20 | |
Imax(8/20)us (kA) | 40 | 40 | 40 | |
Up(kv) | 2.8 | 2.8 | 3 | |
Remote control and indication | ||||
Indication window | ||||
Plug-in Module | ||||
Remote signal control | ||||
Remote signal control | maximum workng voltage(V) | 250 AC/30VDC | 250 AC/30VDC | 250 AC/30VDC |
maximum workng current(A)1A(250V/AC) | 1A(250V/AC) | 1A(250V/AC) | 1A(250V/AC) | |
1A(30VDC) | 1A(30V/AC) | 1A(30V/AC) | 1A(30V/AC) | |
Wiring & installation | ||||
Wiring capacity(mm2) | Hard wire | 4~25 | 4~25 | 4~25 |
Flexible wire | 4~16 | 4~16 | 4~16 | |
Stripping length(mm) | 10 | 10 | 10 | |
Terminal screwa | M5 | M5 | M5 | |
Tarque(Nm) | Main cirult | 3.5 | 3.5 | 3.5 |
Remate signal contact | 0.25 | 0.25 | 0.25 | |
Protection class | All profile | IP40 | IP40 | IP40 |
Connection port | IP20 | IP20 | IP20 | |
Installation environment | NO obvious shock and vibration | |||
Altitude(m) | ≤2000 | ≤2000 | ≤2000 | |
Working Temperatture | -3~+70 | -3~+70 | -3~+70 | |
Relatlve humiclity | 30%~90% | 30%~90% | 30%~90% | |
How to install | Installed with H35-7.5/DIN35 steel mounting rall | |||
Size(mm)(W*H*L) | W | 36 | 36 | 36 |
H | 90 | 90 | 90 | |
L | 70 | 70 | 70 | |
Weight(kg) | 0.24 | 0.24 | 0.24 | |
Technical Data
| Model | MR2-600PV | MR2-1000PV | MR2-1200PV |
Nominal PV system volt | 600V | 1000V | 1200V |
MCOV(UCPV) | 700V DC | 1170V DC | 1200V DC |
Max system discharge Current (8/20us) (Imax) | 40KA | 40KA | 30KA |
Volt protection leve (UP) | ≤ 2.5KV | ≤ 4.0KV | ≤ 4.5KV |
Volt protection Level at 5KA (UP) | ≤ 2.0KV | ≤ 3.5KV | ≤ 4.0KV |
Integrate fuse breaking capacity/interrupting rating | 30KA/1000V DC | 30KA/1000V DC | 30KA/1200V DC |
Technology | Short-circuit interruption (SCI) overcurrent protection | ||
Operating temperature range | -40 to +80 | ||
Nominal discharge current | 12.5KA | ||
Response time (ta) | <25ns | ||
Operating state/fault indication | Green (good) / Red (replace) | ||
Mounting | 35mm DIN Rail per EN 60715 | ||
Degree protection | IP20 | ||
capacity | 3 modules DIN 43880 | ||
Standards Information | IEC61643-11 TYPE2, IEC61643-A Class | ||
Product Warranty | 5 Years | ||
DIMENSION

WORKSHOP

EXHIBITION

FAQ:
Q:How's the delivery?Because I really need them is urgently?
A:For sample order 3~7days will be no problem.And for regular order we promise in 15days.
Q:How's the warranty period for your DC SPD?
A:We offer one year warranty for our customer.
NOTE
T2 PV Surge Protection Device MR-PV series are suitable for photovoltaic applications. These SPDs are designed and tested according to PV T2 classification from IEC 61643-31 & EN 50539-11 standard.