1.Measurement range: 0.9~100002.Measurement speed: finish three phase testing within 35s3.Measurement accuracy:voltage on HV side 0.05%voltage on LV side 0.1%Phase Angle resolution: 0.01°Phase Angle measurement: 0.1°Variable ratio resolution: 0.0001Accuracy of variable ratio measurement: 0.1%(0.9-200)0.2%(200-2000)0.3%(2000-10000)
Brief introduction


According to IEC and relevant national standards, transformer ratio test is a must in the process of power transformer production, handover and maintenance test. This test can supervise the quality of transformer products in the process of delivery and use, and prevent short circuit between turns, open circuit, connection error, internal fault or contact fault of voltage regulating switch.

Our Turns Ratio Meter can measure variable ratio, group number and phase Angle with high accuracy without knowing any parameters of tested power transformer . It's suitable for various transformer testing, such as Z-type transformer, rectifier transformer, furnace transformer, non-hourly shift transformer, equilibrium transformer, Scott transformer and inverse Scott transformer,

Turns Ratio Meter built-in battery, so can conduct test without extra power . With big LCD screen display, very convenient to easy to read data.Turns Ratio Meter can store 1000 groups test data, and transfer it to computer by USB disk.


Features


1.True three-phase test : Single phase power input, internal digital compose into three- phase standard sine wave signal source.Three - phase test power supply is generated through high fidelity power amplifier.

2.With strong function . Not only for single-phase measurement, but also for three-phase winding test automatically , such as polarity and phase angle test . The variable ratio, phase Angle, error, tapping position and tapping value of AB, BC and CA are measured at one time, and the group number can be automatically identified.

3.Phase Angle measurement. Accurate measurement of the phase Angle (0-360°) between the high and low voltage sides, and it can be used to measure the conversion ratio and Angle of non-hourly transformers.

4.Hexagon diagram display function: the test results are displayed by digital and hexagon vector diagram, so that the transformer connection group can be intuitively seen.

5.Blind test function: No need to select connection mode or connection group, no need short-circuit when test Y/△、△/Y transformer, the wiring mode can be automatically switched according to the selected test content .It is possible to measure the variable ratio and group number for transformer without nameplate.

6.Tap test: Turns Ratio Meter can quickly measure the variation ratio and variation ratio error at each tap switch position. Input rated variation ratio one time, he variation ratio error of each tap position can be calculated.

7.With function of measuring turns ratio and operating voltage variation ratio, the operating transformer ratio can more truly reflect the actual value of the voltage transformer under the actual operation.

8.With good vibration resistance ,the use of military connectors enhances the anti-vibration performance.

9.Adopt 5-inch HD LCD screen.

10.Equipped with thermal sensitive high speed micro printer, which can print and save test results at any time.

11.The test source is standard sine digital source ,distortion is less than 0.1%, not effected quality of power supply.

12.Easy to carry: small size, light weight.

13.Equipped with high-capacity lithium ion rechargeable battery, possible to finish 500 times test once full charge.


Technical Parameter


1.Measurement range: 0.9~10000

2.Measurement speed: finish three phase testing within 35s

3.Measurement accuracy:voltage on HV side 0.05%

voltage on LV side 0.1%

Phase Angle resolution: 0.01°

Phase Angle measurement: 0.1°

Variable ratio resolution: 0.0001

Accuracy of variable ratio measurement: 0.1%(0.9-200)

0.2%(200-2000)

0.3%(2000-10000)

4.Fit to use in field

5.Size: 320×240×130

6.Weight: 2.6Kg


Turns Ratio Meter can test transformer category

1. Three-phase transformer ratio test

Before the three-phase transformation ratio test, you should set the parameters first, press the "set" key or select the "parameter setting" item and press "↲" to enter the parameter setting screen to proceed.

Parameter setting, after setting each parameter, press the "exit" key to return to the main interface and select the "three-phase transformer ratio" test option.

2. Three-phase transformer turns ratio test

Before the three-phase turns ratio test, you should set the parameters first, press the "set" key or select the "parameter setting" item and press "↲" to enter the parameter setting screen to proceed.

Parameter setting, after setting each parameter, press the "exit" key to return to the main interface and select the "three-phase turns ratio" test option.

3. Single-phase transformer test

The operation steps are the same as above

4. Z-type transformer test

The operation steps are the same as above,

After the test is completed, the test result is displayed on the screen. The left side of the screen includes: three-phase voltage and phase on the high-voltage side, three-phase voltage phase on the low-voltage side, tap value, ratio value, ratio error, and group judgment test count times And test status. The right side includes the set parameter values and vector analysis diagram.

4. Scott transformer (T type transformer) test

The operation steps are the same as above,

After the test is completed, the test result is displayed on the display screen. The left side of the screen includes: voltage and phase of the three-phase on the high-voltage side, voltage and phase of the three-phase on the low-voltage side, tap value, transformation ratio, transformation ratio error and low-voltage included angle (∠ αβ), the group determines the number of test counts and test status. The right side includes the set parameters and vector diagrams.

5. Reverse Scott transformer (T type transformer) test

The operation steps are the same as above,

After the test is completed, the test result is displayed on the screen. The left side of the screen includes: three-phase voltage on the high-voltage side, three-phase voltage on the low-voltage side, high and low voltage phases, tap value, measured value of transformation ratio, transformation ratio error, group Do not determine the number of test counts and test status. On the right is the hexagonal vector diagram.


F.A.Q.


1. What is your after-sale service

We have 10 seasoned technical engineer as the after-sale service team.it is lead by our duty manager. We promise that our engineer can give answers within 1 hour and deal with equipment failure within 24 hours in time.

2. What’s the warranty period ?

Our warranty period is one year .

The product can be replaced within 1 month, can be repaired for free charge for one year and maintenance for lifetime.

What is more, our warranty can be extended only charged small warranty fee

3.Can you provide the product calibration certificate?

Yes, we can issue our factory calibration certificate.

If you require the third-party calibration certificate, it also can be made,just if through the third party, it will be charged!


Brief introduction


Was established in 2008. It is located in Huading Mould Industrial Park, Economic and Technical Development Zone, Wuhan City, Hubei Province, China, working area more than 4000 square meters, main products included AC/DC hipot tester, transformer testing device, CT/PT analyzer , etc .

1

  Wuhan Goldhome Hi pot Electrical Co.,ltd(short for Goldhome Hi pot) was established in 2008, its predecessor was state-owned third industry enterprises, one of the earliest enterprises specially in develop, design and manufacture high voltage testing equipment in China.In 2016, merged with Wuhan Sang Electric Co., Ltd. , we realize advantageous compartmentalize and resources reorganization.Now it has become a high-tech enterprise integrating R&D, production, marketing installation and commissioning.1.our-historyOur FactoryGoldhome Hi pot is located in Huading Mould Industrial Park, Economic and Technical Development Zone, Wuhan City, Hubei Province, China, working area more than 4000 square meters.As a high-tech enterprise, we are supported by natural advantages from various research universities in Wuhan city. Goldhome Hi pot works closely with professors from State Grid Power Science Research Institute, Electrical Engineering Colleges of Wuhan University and other scientific research institutions, constantly improving technology and updating products . Now Goldhome Hi pot has more than 20 patented technologies, and many software Copyrights!2.our factory-1product and product applicationOur ProductOur advantage products included AC Resonant Test System, PD Free Test System, AC/DC Hi pot Tester, Primary Current Injection, VLF Hi pot Tester, transformer tester,impulse generator,Transformer oil tester,HV Switch gear Tester ,Insulation Tester,ground Resistance Tester,cable fault locator,relay test set,CT PT analyse,arr ester tester and sf6 gas analyzer,etc.Product ApplicationAll the performance indexes of above testing equipment can reach the leading level in China, widely used in power supply bureau, power plant, power construction, railway, petroleum, chemical industry, metallurgy, coal and other industries.In recent years,our factory continues to expand overseas markets, some competitive products are already exported to American and European countries, Africa, Middle East, etc , and well praised by customers.product applicationOur CertificateAll product process is strictly in accordance with international standards and power industry regulations. And the products are through the national, provincial power authorities testing, as well as CE certification! At present,0ur company has received ISO9001:2015 quality management system certification, ISO14001:2018 occupational health and safety management system certification, and ISO14001:2015 environmental management system certification,and also had got SGS certification.We has more than 20 patented technologies,such as The utility model patent of a frequency conversion series resonance test device,The utility model patent of Lightning impulse voltage testing equipment,The utility model patent of DC high voltage generator,The utility model patent of microcomputer relay protection tester,The utility model patent of High voltage switching characteristic tester., etc.4.certificateoverseas market & our serviceOverseas MarketOur products are sold to Europe, Asia, Africa, North and South America and Oceania, Middle East, etc.and are well received by customers.We had won the bids for the purchase of high-voltage no-partial discharge test equipment from the Polish state-owned insulator production plant, the Myanmar National Grid cable fault tester purchase project, and the high-voltage test equipment purchase project of a Russian power installation and test engineering company.We also sell to end customers, and a single device can also be sold. For example, there are power maintenance and installation companies in Indonesia, South Africa, Denmark, and South Korea, and universities and research institutions purchase and use our test equipment.At the same time, our sales targets also include agencies. At present, we already have cooperated with agents in Singapore, Israel, Mauritius , etc.We insist on providing customers with first-class products and first-class services with reliable product quality and perfect service team.5market-1Our service1.Strict factory testAll products will be assembled and test strictly accord with our product process standard. All qualified products will be issued factory release reports and certificate labels.Defect products or non-qualified products won’t be allowed to make deliver.2.Providing technical materialsDuring the product acceptance, we provide the related manual sheets, packing list,qualified certificate labels, factory test reports and other technical documents.3. Support technical guidanceWe also provide the training for the operators. Complete training includes the skilled operations of our equipment, maintenance and troubleshooting . it also ranges the commissioning and test of our products at site!After-sale service1.First-use responsibility systemAfter the product is delivered, the technician can guide the operation at site if the client requires, and be responsible for the first use of each part2.One year warrantyAll products warranty is 1year, life-time maintenance .During the warranty period, if any defects or damaged because of product’s quality, maintenance or replacement can be provided with free charge in order to let our client’s satisfied !3.TroubleshootingIf the troubleshooting is not difficult, and client can handle with it by themselves, we can offer the call-on line guide within 1 hour!If the troubleshooting is difficult to handle with for client, we can promise that the best solution can be provided within 24 hours!