TX3157 E-start/stop button is used to start and stop gas fire-fighting system, and provided with switching function of manual state and auto state. It is normally installed at the position where it is easy for operation at the gate of protection zone.
Overview
After fire is confirmed, smash glass on E-start/stop button and long press “E-start” for one second to send gas spraying request signal to gas fire-fighting control device. Gas fire-fighting control device starts sound-light alarm and turn off air conditioner fan. After delaying, start gas spraying solenoid valve. During the course of delaying, if the person at site confirms no fire or someone at site is not evacuated, press “E-stop” key to stop delaying.
Feature and Benefits
- Electronic encoding: hand-held encoder is used for encoding and it occupies one bus address.
- It is provided with switching function of manual and auto modes, and E-start/stop functions.
Technical Specification
Operating voltage | 15 ~ 28VDC |
Operation current | Monitoring:≤ 3mA Start:≤ 7mA |
Start part type | Reuse type |
Start type | Press “E-start” for 1 second manually |
Stop type | Press “E-stop” for 2 seconds manually |
Conversion mode | Press “conversion key” for 2 seconds manually |
Indicator | Start : red; when the system is in delaying start state, it is on Manual : green; when the system is in manual mode, it is on Auto : green; when the system is in auto mode, it is on Stop : red; when it is in monitoring state, it is not on; when the system is in delaying start stage, press stop button and stop indicator is on; after releasing the button, it is off. |
Encoding type | Electronic encoding |
Operating environment | Temperature:-10°C~55°C |
Relative Humidity | ≦95% RH, non-condensing |
Weight | 1.2kg |
Dimension | 170mm×154mm×55mm |
TANDA Development Pte. Ltd, a world-class commercial fire alarm system solution and service provider, specializing in R&D. manufacturing. marketing OEM/ODM and after-sale service of comprehensive fire system solutions.With its sales network all around the world,TANDA can provide a quick response and high efficiency service locally and its surrounding area.Tanda has established branch offices globally, in location of UK, Dubai ,Malaysia, Vietnam and Mainland China,more than 100 service outlets.TANDA (Singapore) provide clients with one-stop service of fire protection product.As a global company,TANDA has located its production bases in Singapore and Mainland China,total area over 50,000sqm. Numbers of automatic SMT product lines make the annual product ability--20 million detectors and modules, 50 thousand control panels--met customers` demand. All products are strictly in accordance with ISO9001, ISO14001, main products have obtained LPCB, CE certificates.