Membership
Help
Zhejiang Volcano electrical technology Co., Ltd
Zhejiang Volcano electrical technology Co., Ltd

Vacuum interrupter, is the core device of vacuum switch. It uses a pair of electrodes (contacts) and other parts sealed in vacuum, with the aid of excellent insulation and arc extinguishing performance, to realize the closing or breaking of the circuit, and it can quickly extinguish the arc and restrain the current after the power is cut off.
It can be divided into
1. Vacuum interrupters for VCB: rated voltage ranging from 1.14KV to 72.5KV; rated current ranging from 630A to 2500A; rated short circuit breaking current ranging from 12.5KV to 8KA.
2. Vacuum interrupters for LBS: rated voltage ranging from 7.2KV to 40.5KV; rated current ranging from 630A to 1250A; rated short time withstand current ranging from 12.5KA to 25KA.
3. Vacuum interrupters for contactors: rated voltage ranging from 1.14KV to 40.5KV; rated current ranging from 630A to 1250A.
4. Vacuum interrupters for recloser: rated voltage ranging in 12KV, 15KV, 27KV, and 38KV; rated current from 400A to 630A; and rated short circuit breaking current from 10KA to 20KA.
6. Epoxy embedded poles: rated voltage from 12KV, to 40.5KV; rated current from 630A to 3150A; rated short circuit breaking current from 20KA to 50KA.
There are many structural types of vacuum interrupter, but no matter which structural type is adopted, it is composed of air tight insulation system, conductive system, shielding system, bellows, conductive rod, fixed element, guide sleeve and other parts and components.
Product advantages:
1.Once Seal-Exhaust Technique
2.Free painting technology
3.316L Stainless steel, easy-welding and environmental friendly .
4.Good quality &competive price


Technical data
Items | Value |
Rated Voltage | 40.5KV |
Lightning Impulse withstand voltage(peak) | 185KV |
Short time power frequency withstand voltage (1 min) | 95KV |
Rated frequency | 50HZ |
Rated current | 2500A |
Rated short time withstand current | 25KA |
Rated duration of short circuit | 4s |
Rated peak withstand current | 63KA |
Rated short circuit breaking current | 63KA |
Rated short circuit breaking current | 25KA |
Rated short circuit current breaking times | 30 Times |
Rated breaking current of single capacitor bank | 400A* |
Mechanical life | 10000 Times |
Clearance between opening contacts | 22±2mm |
Closing force due to bellow and atmosphere | 250±50N |
Force required to hold contacts open at full stroke | 330±60N |
Circuit resistance at minimum rated contact force | ≤15μΩ |
Contacts limit abrasion | 3mm |
Weight of moving parts | ≤3kg |
Mechanical requirements
Items | Value |
Average opening speed | 1.8±0.2m/s |
Average closing speed | 0.8±0.2m/s |
Contacts bouncing duration at closing operation | ≤3ms |
Synchronism of contact closing and opening | ≤1ms |
Rated contact pressure | 3150±200N |