Membership
Help
Zhejiang Volcano electrical technology Co., Ltd
Zhejiang Volcano electrical technology Co., Ltd
Product description
The vacuum interrupters of VS1 type vacuum circuit breaker are used embedded poles by advance APG technology;the primary conducting part is capsulated into an integrated unit by using epoxy resin which makes the insulation condition of primary conducting parts against from impact by exterior enviroment,it can effectively prevent moisture,filths and the damage to the insulation property due to condensed water.
The vacuum interrupter is vertically installed in an insulation house which is made up og epoxy resin cast by advanced APG technology;this kind of structure can maximally reduce the dust accumulation on the surface of vacuum interrupters which ensure the high resitance state even if under the damp,hot and serious filthy enviroment.
The VS1 type vacuum circuit breaker uses specialized vacuum interrupter with advanced material and design for their contact, it is with strong breaking capability and high reliability and performed the type test for its electrical life under the condition of autore-close at class E2 level(the breaking operations reaches 274 times for different shor-circuit currents)as per national standard,it is more accordance with the actural usage requirement and realized free of maintenance for its primary part.
Outline drawing


Main Technical Specification
| S.N | Name | Unit | Data | |||||||
| 1 | Rated voltage | kV | 12 | |||||||
| 2 | Rated current | A | 630 | 1250 | ||||||
| 3 | Rated short circuit breaking current | kA | 20 | 25 | 20 | 25 | 31.5 | 40 | 31.5 | 40 |
| 4 | Rated peak withstand current | kA | 50 | 63 | 50 | 63 | 80 | 100 | 80 | 100 |
| 5 | Rated short time withstand current | kA | 20 | 25 | 20 | 25 | 31.5 | 40 | 31.5 | 40 |
| 6 | Rated short circuit making current | kA | 50 | 63 | 50 | 63 | 80 | 100 | 80 | 100 |
| 7 | Switching operations of short circuit current | Cycle | 50 | 30 | ||||||
| 8 | Rated operating sequence | O-0.3s-CO-180s-CO,O-180s-CO-180s-CO(40kA) | ||||||||
| 9 | Mechanical endurance | Cycle | 30000 | |||||||
| 10 | Rated breaking operations of rated current | Cycle | 20000 | |||||||
| 11 | Rated lighting impulse withstand voltage | kV | 75 | |||||||
| 12 | Rated power frequency withstand voltage | kV | 42 | |||||||
| 13 | Contact stroke | mm | 9±1 | |||||||
| 14 | Overtravel of contacts | mm | 3.5±0.5 | |||||||
| 15 | Closing speed | m/s | 0.4±0.8 | |||||||
| 16 | Main circuit resistance of each pole | μΩ | ≤40 | ≤45 | ≤40 | ≤35 | ||||
| 17 | Opening speed | m/s | 0.9~1.3 | |||||||
| 18 | Contact bouncing duration at closing operation | ms | ≤2 | |||||||
| 19 | Simultaneity of three phase closing and opening | ms | ≤2 | |||||||
| 20 | Closing time | ms | 35~70 | |||||||
| 21 | Opening time | ms | 20~50 | |||||||
| 22 | Distance between phases | mm | 150,210,275 | |||||||
| 23 | DC component | 50% | ||||||||
Packaging&Delivery
| Packaging details | Each one is wrapped with plastic film in non-solid wooden case. |
| Delivery details | Within 15 days from the date of receiving signed sales confirmation by both parties. |
Company introduction
Zhejiang Volcano Electrical Technology Co., Ltd, located in economic development zone, Yueqing, near to elecrical town Lishi, is always focusing on developing, manufacturing and selling 10-40.5 kV mediun and high voltage electrical equipments. The company produces electrical parts like VCB, ACR and LBS, and aslo customerized complete set such as medium voltage switchgear. With main pricipal of company, to get a win-win solution, quality is always ranked first.