Membership
Help
Zhejiang Anfu New Energy Technology Co.,Ltd.
Zhejiang Anfu New Energy Technology Co.,Ltd.



KYCM2PLC series intelligent miniature circuit breakers have the characteristics of advanced and reasonable structure, reliable performance, high breaking capacity, and beautiful appearance. The shell material is composed of high-quality impact-resistant and high-flame retardant materials. It is suitable for indoor, AC 50Hz, rated voltage 230V, three-phase 400V, and rated current not exceeding 100A. It is mainly used for low-voltage terminal power distribution in industrial, commercial, civil buildings and infrastructure in buildings and similar places. Leakage, overload, short circuit, over-under-voltage, over-heating, and lack of equal protection can also be used for infrequent on-off operations. The leakage circuit breaker with the rated residual operating current less than 30mA can provide protection for personal electric shock.
| Number of poles | 1P, 2P, 3P, 4P |
| Breaking capacity | 1A-63A, 10kA |
| 80-100A, 6kA | |
| Rated voltage | 230/400V AC |
| Rated current | 1A-100A |
| Residual current type | A type, AC type |
| Residual current specifications | 30, 100, 300mA or adjustable |
| Trip time | Standard type, time delay type, adjustable type |
| Configurable leakage function | Shut down, alarm, alarm and protection |
| Leakage self-test | Automatic non-trip self-check, remote and local trip self-check |
| Short circuit protection | Type B, Type C, Type D |
| Trip time | <0.1s |
| Overcurrent protection | Thermal element + electronic |
| Thermal trip | Inverse time limit |
| Electronic trip | Inverse time or definite time |
| Working current | Electronically adjustable |
| Overvoltage protection | JB/T 12762 OUPA standard |
| Overvoltage setting value | 275V |
| Undervoltage setting value | 0.7Ue |
| Action time | Standards compliant |
| Meet the standard | Shut down, alarm, alarm and protection |
| Terminal temperature rise protection | Alarm + protection |
| Temperature rise alarm setting value | >50K |
| Temperature rise action setting value | >60K |
| Action time | 15min |
| Temperature rise protection function can be configured | Shut down, alarm, alarm and protection |
| Three-phase unbalance | Monitoring + alarm |
| Lack of phase | Monitoring + alarm + protection |
| Configurable function | Shut down, alarm, alarm and protection |