XBC diesel fire pump set for a new fire control equipment of the company strictly in accordance with the national standard GB6245-98 "fire pump performance requirements and test methods" and American Fire Protection Association standard NEPA20 "installation of centrifugal fire pumps" and other standards developed by the (hereinafter referred to as the equipment), the equipment according to the fire pump matched (single stage single suction, single stage double suction, segmental multi-stage) can be divided into XBC-IS, XBC-SLOW, XBC-D and other three sub, pressure equipment, wide flow range, the application can meet almost all occasions the fire required. Equipment with diesel engine adopts domestic or imported high-quality products, has a good performance of start-up, strong overload capacity, compact structure, convenient repair, simple use, high degree of automation features, is a kind of fire fighting equipment advanced, reliable performance. Equipment in normal operation condition: the height above sea level is less than or equal to 1000m; the environment temperature: +5 degrees ~+40 degrees; air relative humidity is less than or equal to 90%.
The structure characteristics and function description:
Equipment by X6135, 12V135, 4102, 6102 diesel engine, diesel engine (can match the clutch) by high elastic coupling with the fire pump is connected and combined into a fire pump set, the unit also includes a diesel tank, cooling water tank, the fan, control panel (automata group) etc..
When the automatic control unit, automatic control cabinet is composed of a split type diesel engine (programmable) to realize the system automatically to the first degrees years, input, automatic switching (electric pump set to switch to diesel pump group or the group of diesel pump group switch to another group of diesel pump group), automatic protection (diesel overspeed, low oil pressure, high, hydrological three times failed to start, low oil level, low battery voltage alarm shutdown protection) and other functions, and users can also fire center or automatic fire alarm device interface, the realization of remote monitoring and control.
In order to ensure the normal work of the unit below 5 DEG C environment, the unit can be attached to the AC220V cooling water heating device.
General data
Diesel fire leap Group and electric pumps, voltage stabilizing pump etc. the automatic fire water supply system. See "the working process of diesel engine control system" is introduced. The device can control and fire control center to realize.
The way of water inlet fire pump self suction irrigation and two, according to the fire code requirements, generally from the irrigation water diversion. If the user needs to suction inlet system, need to specifically in order to provide automatic vacuum water diversion device company, but the pump group size change.
The system structure and the principle of
1 LED-BZ (H) diesel pump group control system design
General data
Automatic fire water supply system usually consists of electric pump pump regulator, (main pump), automatic diesel pump (pump), the principle of work is: the normal pressure of pipe network in P1 (low voltage) ~P2 (high pressure) between, below the P1 voltage stabilizing pump start, stop the pump pressure up to P2, because the network leakage P2 slowly decreased to P1, voltage stabilizing pump and starting, so reciprocating pressure maintained at between P1~P2, when the water increase, voltage stabilizing pump to maintain P1 soon fell to P3, the electric pump is started, the pressure up to Pw and meet the water for fire fighting. If a power outage or electric pump failure, pressure by P3 continued to decline to P4 diesel engine starting automatic pump, pressure up to Pw and water supply, electric pump or diesel pump stop pump must manually after artificial judgment to stop the pump, such as the estimation of pipe leakage more, would increase the pressure stabilizing tank or pump regulator normally open, in order to start frequent.
(1) equipment control pump of LEC-BH semi automatic fire diesel
该型电控柜(箱)具备手动、半自动控制功能,具有柴油机油压、水温显示功能;具备蓄电池充电电流显示;油箱油位过低报警;火警状态电动泵故障或停电的情况下,可自动启动柴油机泵;可远程起动柴油机泵。此种控制方式一般用在柴油机功率小于110kw的场合下。
This type of control cabinet (box) with manual, semi automatic control function, with diesel engine oil pressure, water temperature display function; have the battery charging current display; oil tank level low alarm; fire state electric pump failure or power outage, can automatically start the engine pump; remote starting diesel engine pump. This control method is generally used in diesel engine power is less than 110KW of the occasion.
(2) LEC-BZ full automatic fire pump control device of diesel engine
This type of control cabinet (box) with manual, automatic control function, with diesel engine oil pressure, oil temperature, water temperature display and alarm of abnormal function, have the battery charging current display; oil tank level low alarm; automatic (or remote) stop diesel pump; super high speed, super low speed shutdown alarm; three times starting failure alarm; low battery voltage automatic charging; and with the fire center or automatic fire alarm device an excuse to realize remote control linkage, such as a system for multiple pump units, but also can realize the switching between the unit and the fire pump regularly patrol, frequency constant pressure function (but this function need user specified in the contract), the control mode generally used in the diesel engine power is more than 110KW of the occasion.
2 LEC-DZ (H) diesel generator control device
Control principle is similar to diesel pump configuration control of diesel engine diesel generator, mainly applicable to the civil construction of the generator voltage to own emergency diesel generator 230V/400V, own emergency engine group should at any time in a ready to start status, operational power supply, thermal system, fuel oil, lubricating oil, cooling water and indoor temperature and indoor environment shall ensure that the unit can start conditions, when the electricity is interrupted, the unit should immediately start, and can be put into normal load operation in 15s. Units should be in power system of chain, when the city electricity is restored, the unit should delay switching to electric power supply, automatic parking and idle 3~5min.
General data
(1) the LEC-DH control equipment according to automatic diesel generating set
This type of control cabinet (box) with manual, semi automatic control function, with diesel engine oil pressure, old asked display function; have the battery charging current display; oil tank level low alarm; semi automatic work, the need for manual opening of diesel engine, and by artificial the speed to rise to the rated speed of the diesel engine, electric generator to generate when normal later, by the artificial closed circuit breaker of power to the load, generator outages also need manual shutdown.
(2) control device of LEC-DZ automatic diesel generating set
This type of control cabinet (box) with manual, automatic control function, with diesel engine oil pressure, oil temperature, water temperature display and alarm function has a teahouse, battery charging current display; oil tank level low alarm; automatic (or remote) stop generator; super high speed, super low speed listening machine of three starting alarm; failure alarm; low battery voltage automatic charging; and with difficulties stubborn center device excuse, to realize the remote control linkage. The automatic work of the system, by the programmable logic controller (PLC) control, generator starting to load and power supply, and stop the generator work by PLC automatic control. Automatic stop abnormal fault system.
The model significance
XBC 8 – 50 / IS
XBC 8 - 50 / IS
Type fire pump
Pump rated flow (L/s)
10 times the rated pressure of the pump (MPa)
Diesel fire pump set
Scope of application: equipment suitable for warehouses, docks, airports, petrochemical, power plants, liquefied petroleum gas, textiles, ships, oil tankers and other occasions of fire water supply.
The working conditions of altitude is less than or equal to 1000m; the environment temperature: +5 degrees ~+40 degrees; air relative humidity: less than or equal to 90%.