YBNA-DC1000/40.5-1000 integrated prefabricated substation is developed by our company by combining domestic and foreign advanced technology experience with our own advantages, which is used for photovoltaic power generation. It not only saves the equipment cost, but also saves a lot of land, materials and human resources for substation construction. The substation can convert DC produced by PV arrays into 40.5kV high voltage AC. Due to the compactness, reliability, short construction period, simple installation and less cost, the substation is widely used in integrated photovoltaic substation distribution system.
This product conforms to such standards as GB/T 17467-2010 “High Voltage and Low Voltage Prefabricated Substation” and JB/T 10217-2013 “Padmounted Transformer” and so on.
YBNA-DC1000/40.5-1000 integrated prefabricated substation is arranged in “目” shape. It has the advantages of compact structure and attractive appearance. Its color can be determined according to user’s requirements, and is easy to integrate with the external environment;
The substation adopts metal-enclosed enclosure.The base is welded by U-steel, then undergoes electrophoresis and paint spraying. It has the advantages of strong corrosion resistance and sufficient mechanical strength;
The enclosure has good heat insulation, protection against rain and radiation and ventilation effect (natural air cooling at HV side and forced air cooling at LV side).
No. | Item | Unit | Parameter | ||
1 | Rated voltage at high voltage side | kV | 40.5 | ||
2 | Rated voltage at low voltage side | V | 315 | ||
3 | Rated voltage at incoming side | V | DC1000 | ||
4 | Rated power-frequency short-duration (1min) withstand voltage of low voltage AC connector wire | kV | 2.5 | ||
5 | Rated lightning impulse withstand voltage of low voltage AC connector wire | kV | 7.4 | ||
6 | Rated power-frequency short-duration (1min) withstand voltage of HV connector wire | kV | 95 | ||
7 | Rated lightning impulse withstand voltage of HV connector wire | kV | 185 | ||
8 | Rated power-frequency short-duration (1min) withstand voltage of auxiliary and control circuit | kV | 2.0 | ||
9 | Rated power-frequency short-duration (1min) withstand voltage of low voltage DC connector wire | kV | 2.6 | ||
10 | Rated frequency | Hz | 50 | ||
11 | Rated current at HV side | A | 31.5 | ||
12 | Rated current at LV side | A | 1250 | ||
13 | Rated continuous working current at DC side of inverter | A | 1008 | ||
14 | Rated short-time withstand current at LV side | Main circuit | kA/s | 50/1 | |
Earthed circuit | kA/s | 20/2 | |||
15 | Rated peak withstand current at LV side | Main circuit | kA | 105 | |
Earthed circuit | kA | 50 | |||
16 | Rated voltage of auxiliary and control circuit | V | AC220、DC220 | ||
17 | Rated frequency of auxiliary and control circuit | Hz | 50 | ||
18 | Rated capacity of the transformer | kVA | 1000 | ||
19 | Total loss of transformer under rated condition | W | 13450 | ||
20 | Rated enclosure level | / | 0 | ||
21 | Inverter efficiency | % | 98.7 | ||
22 | Mechanical protection class | / | IK10 | ||
23 | Cooling mode of substation | High voltage compartment | / | A.C | |
Transformer | / | ONAN | |||
Low voltage compartment | / |
F.A.C | |||
24 | Protection class of enclosure | / | IP44 | ||