General parameters
| System Power | Power supply: 9-36Vdc (Nominal:24Vdc)Protection: overcurrent protection, anti-reverse connection protection |
| Power Consumption | 50mA@24Vdc |
| Internal bus power supply current | Max:2.5A@5VDC |
| Isolation | System Power to Field Power: Isolation |
| Field Power | Range:22-28Vdc(Nominal:24Vdc) |
| Field Power Current | Max.DC 8A |
| IO Modules Supported | 32 pcs |
| Wiring | Max.1.5mm²(AWG 16) |
| Mounting Type | 35mm DIN-Rail |
| Size | 115*51.5*75mm |
| Weight | 130g |
Environment Specification
| Operational Temperature | -40~85℃ |
| Operational Humidity | 5%~95% RH(No Condensation) |
| Protection Class | IP20 |
Interface Parameter
Note: M represents the valid parameters of master mode, S represents the valid parameters of slave mode, and F represents the valid parameters of free transparent transmission mode
| Programming Specification | |
| Programming Software | CIACON |
| Program Storage | 127KBytes |
| Data Storage Unit | 52KByte |
| Run-Time System | Multiple PLC Task |
| Programming Language | IEC 61131-3 (LD, IL, ST, FBD, SFC) |
| RTC | Supported |
| Max. Task | 3 |
| Max. Cyclic Task | 3 |
| Max. State Task | 3 |
| Scanning Time | 1ms |
| Interface Parameters | |
| Max. Extension Module | 32 |
| Max. Input Size | 512 Word(1024Byte) |
| Max. Output Size | 512 Word(1024Byte) |
| Max. Nodes Number | Restricted by the Ethernet specification |
| Baud Rate | 10/100Mbps, Self-adaptive, full duplex |
| Network Protocol | Modbus TCP、Modbus RTU |
| serial Port Configuration(RS485) | Modbus RTU,Baud Rate:2400~115200bps |
| LED Indicator | 6 pcs of LED Indicator PWR STAT RUN ERR IRN IER |