1.Introduction:
Voltage transducers convert AC input into load independent DC current & voltage output signal. This signal is highly accurate & proportionally linear to the AC input. GPV versions convert the AC sinusoidal waveforms to linear DC output calibrated to the RMS value.
Current transducers convert AC input into load independent DC current & voltage output signal. This signal is highly accurate & proportionally linear to the AC input. GPA versions convert the AC sinusoidal waveforms to linear DC output calibrated to the RMS value.
2.Applied Standards & Rules:
Measuring and conversion:IEC 688 / 1992 - 04
Dielectrical strength:IEC 688 2KVac/1 min.
Surge and Impulse test:ANSI C37.90 / 1989;IEC 255-3 (1989) 4KV1.2x50us
3.Specification
Reference Standard: | GB/T 13850-1998(IEC688-1992) |
Accuracy: | 0.5%RO according to IEC 688-1,At(23±5℃) |
Long term stability: | ≤±0.5%/year,No accumulation error |
Temperature influence: | <100ppm/℃ |
Response Time: | <400ms |
Output Ripple: | <1.0% (peak-peak value) |
Input burden: | Current less 0.2VA;voltage less 0.1VA |
Frequency: | Nominal frequency ±10% |
Maximum output load: | Current output Max10V pressure drop Voltage output rated 2mA MAX 5mA output |
Auxiliary power: | < 3VA (for GPA & GPAR);< 8VA (for GPAX); |
Auxiliary load effect: | <0. 2 % |
Allow excessive input: | Current 2 rate continuous 20 rate 1 secs voltage max 2 rate continuous |
Dielectric strength: | Input/output/power/betwem the crust 2KV,AC 1 min IEC866 |
Impact test: | ANSI C37.90a/1973,IEC 255-4,(5kV 1.2/50us Pulsed Voltage) |
Calibration amplitude: | Full scale least<±3%,zero least<±1% |
Magnetic field effect: | 0.4KA/m magnetic field strength change<0.05% |
Operating condition: | Temperature -10~55℃relative humidity ≤95% RH non condensing |
Storage condition: | Temperature-40~70℃ relative humidity ≤95% RH non condensing |
4.Models and specifications:
4.1AC VOLTAGE TRANSDUCERS
GPVS :single phase self-powered voltage
GPVXS: three phase self-powered voltage
GPV2 : single phase,2 wires / 4~20mA ( 8~36V DC powered )
GPVX2: three phase,2 wires / 4~20mA ( 8~36V DC powered )
GPV : 1 unit of avg. to rms conversion
GPVX : three phase voltage
GPVR : single phaseTure rms conversion
GPVT : single phase Dual output
4.2 AC CURRENT TRANSDUCERS
GPAS:single phase self-powered current
GPAXS:three phase self-powered current
GPA2:single phase,2 wires / 4~20mA ( 8~36V DC powered )
GPAX2: three phase,2 wires / 4~20mA ( 8~36V DC powered )
GPA:1 unit of avg. to rms conversion
GPAX:three phase voltage
GPAR:single phaseTure rms conversion
GPAT :single phase Dual output
5.Terminal Connection:

6. Dimensional Drawings:
6.1 GPA.GPV,GPAS.GPVS