1. Model:
S3-WD-1: 1φ2W active power transducer, accuracy : 0.2% RO
S3-WD-1S : 1φ2W active power transducer, accuracy : 0.2% RO, (dual output)
S3-WD-3: 3φ3W active power transducer, accuracy : 0.2% RO
S3-WD-3S : 3φ3W active power transducer, accuracy : 0.2% RO (dual output)
S3-WD-3A: 3φ4W active power transducer, accuracy : 0.2% RO
S3-WD-3AS: 3φ4W active power transducer, accuracy : 0.2% RO (dual output)
N3-WD-1: 1φ2W active power transducer, accuracy : 0.5% RO
N3-WD-1S : 1φ2W active power transducer, accuracy : 0.5% RO, (dual output)
N3-WD-3: 3φ3W active power transducer, accuracy : 0.5% RO
N3-WD-3S : 3φ3W active power transducer, accuracy : 0.5% RO (dual output)
N3-WD-3A: 3φ4W active power transducer, accuracy : 0.5% RO
N3-WD-3AS: 3φ4W active power transducer, accuracy : 0.5% RO (dual output)
2.Order form:

3. Example of model and parameter filling:
(1) N3-WD-3-555A4BY
0.5%RO, 3φ3W active power transducer
Input nominal current: 5A; input nominal voltage: 100V;
Nominal input power 2: 866W;
Input signal frequency: 50±5Hz;
Output range: 4~12~20mA;
Correspondence -866~0~866W
Auxiliary power supply: AC220V.
Need to measure the reverse power.
(2) S3-WD-3-155A3BN
0.2%RO, 3φ3W active power transducer
Input nominal current: 1A;
input nominal voltage: 100V;
Nominal input power 2:170W;
Input signal frequency: 50±5Hz;
Output range: 0~20mA;
Corresponding 0~170W
Auxiliary power supply: AC220V.
There is no need to measure reverse power.
(3) S3-WD-3A-525V5BY
0.2%RO, 3φ4W active power transducer
Input nominal current: 5A;
input nominal voltage: 220V;
Nominal input power 2: 3300W;
Input signal frequency: 50±5Hz;
Output range: -10~0~10V;
Correspondence -3300~0~3300W
Auxiliary power supply: AC220V.
Need to measure the reverse power.
Note:
1 The value in the output range () is the value specified for positive and reverse power output.
2 system power calibration:
Single phase is the input nominal voltage × input nominal current;
The three-phase three-wire system is double the input nominal voltage × input nominal current;
Three-phase four-wire system is 3 times the input nominal voltage × input nominal current;
Calibration of non-nominal power: usually keep the input voltage at the nominal value,
The required power rating is obtained by changing the input current.
The output of the 3 dual output is 1 (+) and 2 (-) terminals.
4 If the user needs other special calibration, please indicate the parameter value in the contract.