GPW/GPK active power / reactive power transducer
GPWK active power / reactive power combined transducer
GPWA/GPKA active power current / reactive power current combination transducer
1.Introduction:
Time-division-multiplication (TDM) principle of computing the AC power inputs to a corresponding DC output value. The measurements of active power of single or three phase balanced or unbalanced systems, are precisely converted to a highly accurate linear DC voltage or current output.
Applied Standards & Rules:
Measuring and conversion:IEC 688 / 1992 - 04
Dielectrical strength:IEC 688 2KVac/1 min.
Surge and Impulse test:ANSI C37.90 / 1989,IEC 255-3 (1989) 4KV1.2x50us
2.Models and specifications:
GPW101: 1 phase 2 wires watt
GPW201: 3 phase 3 wires watt
GPWT201: 3 phase 3 wires watt(Dual output)
GPW301: 3 phase 4 wires watt
GPWT301: 3 phase 4 wires watt(Dual output)
GPK201: 3 phase 3 wires Var
GPKT201: 3 phase 3 wires Var(Dual output)
GPK301: 3 phase 4 wires Var
GPKT301: 3 phase 4 wires Var(Dual output)
GPWK201: 1 phase 2 wires watt&Var
GPWKA201:3 phase 3 wires watt&Var&1Current
GPWK301: 3 phase 4 wires watt&Var
3.Specification
Reference Standard: | GB/T 13850-1998(IEC688-1992) |
Accuracy: | 0.5% |
Long term stability: | ≤±0.5%/year,No accumulation error |
Temperature influence: | <100ppm/℃ |
Response Time: | <400ms |
Output Ripple: | <1.0% (peak-peak value) |
Input burden: | Current less 0.2VA;voltage less 0.1VA |
Frequency: | Nominal frequency ±10% |
Maximum output load: | Current output Max10V pressure drop Voltage output rated 2mA MAX 5mA output |
Auxiliary power: | WATT unit: <3.5VA,VAR unit <3.5VA,Current unit <3VA. |
Auxiliary load effect: | <0. 2 % |
Allow excessive input: | Current 2 rate continuous 20 rate 1 secs voltage max 2 rate continuous |
Dielectric strength: | Input/output/power/betwem the crust 2KV,AC 1 min IEC866 |
Impact test: | ANSI C37.90a/1973,IEC 255-4,(5kV 1.2/50us Pulsed Voltage) |
Calibration amplitude: | Full scale least<±3%,zero least<±1% |
Magnetic field effect: | 0.4KA/m magnetic field strength change<0.05% |
Operating condition: | Temperature -10~55℃relative humidity ≤95% RH non condensing |
Storage condition: | Temperature-40~70℃ relative humidity ≤95% RH non condensing |