2. Example of model and parameter filling:
(1) S3-WHW-3-555A43CB
0.2%RO 3φ3W active power / active energy transducer
Input nominal current: 5A;
Input nominal voltage: 100V;
Nominal input power: 866W;
Input signal frequency: 50±5Hz;
Output range (power): 4-20mA/ 0-866W;
Output range (power constant): 10000 pulses / kWh
Output type: no voltage pure contact (optocoupler open collector output);
Auxiliary power supply: AC220V.
(2) N3-WHW-3-155V23CB
0.5%, 3φ3W active power / active energy transducer
Input nominal current: 1A;
Input nominal voltage: 100V;
Nominal input power 4:170W;
Input signal frequency: 50±5Hz;
Output range (power): 0-5V/0-170W;
Output range (power constant): 1000 pulses / kWh
Output type: no voltage pure contact (optocoupler open collector output);
Auxiliary power supply: AC220V.