| Input | Voltage stabilization range
| Three-phase 304V-456V, single-phase 176V-264V |
| Frequency | 50HZ/60HZ |
| Output | Rated voltage | Phase voltage 220V, line voltage 380V |
| Center voltage | ±7% |
Accuracy of voltage stabilization
| ±5% |
| Response time | ≤50ms |
| Waveform distortion | No additional waveform distortion (static) |
| Efficiency | ≥98% |
Three-phase unbalanced degree
| Three-phase voltage balance automatically |
| Time delay output | Voltage stabilization output first (protect equipment from impact) |
| Over-voltage | When output phase voltage is beyond 10% (245), it cuts off the output, or turns to bypass uninterruptedly
|
| Under-voltage | When output phase voltage is lower than 10% (198), it cuts off the output, or turns to bypass uninterruptedly
|
| Protection | Open-phase | With automatic cut off function |
| Overload | Electronic detector, cut off the output in 3min in case of overload |
| Over-current | Dual protections of electronic detector and circuit breaker |
| Short-circuit | Dual protections of electronic detector and circuit breaker |
| Bypass | By manual, or automatic bypass uninterruptedly |
| Indicator | Voltage | A, B, C and ΣABC three phases have TRMS digital display respectively |
| Current | A, B, C and ΣABC three phases have TRMS digital display respectively |
| Working status | Voltage stabilization status and utility power status |
| Abnormal | Over-voltage, under-voltage, overload, fuse blowout |
| Working mode | Two modes: voltage stabilization and utility power |
| Overload capacity | 5 times the rated current for 1s |