ACSR with CSA C49 StandardSTANDARD:CSA C49 StandardDELIVERY LENGTH:accord with the requestCAPACITY:2000km/monthMIN ORDER QTY:1kmDOWNLOAD PDF: 4.49 MBSEND E_MAILGET PRICE
Application
The conductors are suitable for use in all practical spans on wood poles, transmission towers,and other structures. Application range from extra high voltage(EHV) transmission lines to sub-service spans at distribution or utilization voltages on private premises.
Aluminum 1350 wires and the steel cores are concentrically stranded and wrapped helically around a central wire. The additional corrosion protection is available through the application of grease to the cores or infusion of the complete cable with grease.
Specification
Code Name | KCMIL or AWG | Cross Section | Steel Ratio | Stranding Wires | Dia.of Core | Overall Dia. | Linear Mass | Rated Tensile Strength | Max.D.C. Resistance at 20℃ |
Alum. Wire | Steel Wire |
Alum. | Total | No. | Dia. | No. | Dia. |
- | - | mm² | mm² | % | - | mm | - | mm | mm | mm | kg/km | kN | Ω/km |
Wren | 8 | 9.37 | 9.76 | 17 | 6 | 1.33 | 1 | 1.33 | 1.33 | 3.99 | 33.8 | 3.29 | 3.43 |
Warbler | 7 | 10.55 | 12.32 | 17 | 6 | 1.5 | 1 | 1.5 | 1.5 | 4.5 | 42.8 | 4.14 | 2.72 |
Turkey | 6 | 13.3 | 15.51 | 17 | 6 | 1.68 | 1 | 1.68 | 1.68 | 5.04 | 53.8 | 5.19 | 2.158 |
Thrush | 5 | 16.77 | 19.57 | 17 | 6 | 1.89 | 1 | 1.89 | 1.89 | 5.67 | 67.9 | 6.56 | 1.711 |
Swan | 4 | 21.15 | 24.68 | 17 | 6 | 2.12 | 1 | 2.12 | 2.12 | 6.36 | 85.6 | 8.15 | 1.357 |
Swallow | 3 | 26.66 | 31.11 | 17 | 6 | 2.38 | 1 | 2.38 | 2.38 | 7.14 | 107.9 | 10 | 1.076 |
Sparrow | 2 | 33.63 | 39.22 | 17 | 6 | 2.67 | 1 | 2.67 | 2.67 | 8.01 | 136 | 12.4 | 0.8534 |
Robin | 1 | 42.41 | 49.48 | 17 | 6 | 3 | 1 | 3 | 3 | 9 | 171.6 | 15.3 | 0.6766 |
Raven | 1/0 | 53.51 | 62.43 | 17 | 6 | 3.37 | 1 | 3.37 | 3.37 | 10.11 | 216.5 |
|