Natural Gas Turbine flow meter measure the velocity of natural gas in pipes, such as High accuracy turbine flow meters are available for custody transfer of natural gas. These flow meters often incorporate the functionality of a flow computer to correct for pressure, temperature and fluid properties in order to achieve the desired accuracy for the application.it will transfer the actual flow rate to standard flow rate by the detected pressure and temperature.The Natural Gas Turbine Flow Meter now is widely used in ......
Product Details
Natural Gas Turbine Flow Meter
Natural Gas Turbine flow meter measure the velocity of natural gas in pipes, such as High accuracy turbine flow meters are available for custody transfer of natural gas. These flow meters often incorporate the functionality of a flow computer to correct for pressure, temperature and fluid properties in order to achieve the desired accuracy for the application.it will transfer the actual flow rate to standard flow rate by the detected pressure and temperature.The Natural Gas Turbine Flow Meter now is widely used in the trade calculation of natural gas and other kinds of fuel gases.
Main Application
Natural Gas,LPG,Compressed Air,Nitrogen
Nominal Diameter
DN25-DN300
Span
2.5-6500m³/h
Rated Pressure
1.6MPa~4.0MPa
Accuracy Level
±1.5%R 1.0% Selectable
Repeatablility
±0.1%
Range Ration
1:10,
Material
Body/Rotor Support:SS304(SS316L optional)
Impeller:Double Phase Steel
Shaft:Stainless Steel
Bearing:Stainless Steel Ball Bearing
Process Connection
Flange/Thread NPT/Wafer
Working Condition
Medium Temperature:-20℃~+80℃
(Max Customize to150℃)
Ambient Temperature:-20℃~+60℃
Rated Humidity:5%~90%
Ambient Pressure:86KPa~106KPa
Power
24VDC
3V 10AH lithium battery.
Consumption
24VDC power:<1W
Battery:≤1W,lifetime>3yrs
Signal Output
Pulse,4-20mA,Switch Signal.
DIgital Communication
RS485,MODBUS,HART,PROFIBUS-DP
Signal wire joint
Hausman joint/Inner screw M20*1.5 or customized
Explosion Proof Grade
ExdIIBT6/ExiaIICT4
Degree of Protection
IP65 or Higher
Installation requirements for Natural Gas Turbine Flow Meter
Before the installation of gas turbine flowmeter: the pipeline shall be purged to prevent the residual iron from affecting the normal operation of flowmeter. Before installation, when the turbine is driven by micro air flow, the turbine can rotate flexibly without irregular noise, the counter can rotate normally without interruption and stagnation, so the gas turbine flowmeter can be installed and used normally.
When installing the gas turbine flowmeter: a sealing washer shall be added between the flange and the pipe flange. Filter shall be installed in front of gas turbine flowmeter, and oil filter shall be installed in case of dirty gas quality. Before ordering, users can order from our company at the same time. It is strictly prohibited to connect the filter and gas turbine flowmeter directly.
Gas turbine flowmeter shall be equipped with stop valve before and after installation. There should be no protrusions at the inner diameter of the pipe at the flange connection.
During the installation of gas turbine flowmeter, it is strictly prohibited to directly weld at its inlet and outlet flange to avoid burning the internal parts of flowmeter.
The gas turbine flowmeter shall be installed in a place convenient for maintenance, without strong electromagnetic field, mechanical vibration and thermal radiation;
Gas turbine flowmeter should not be used in the situation of frequent flow interruption and strong pulsating flow or pressure pulsation;
When the gas turbine flowmeter is installed outdoors, the upper part shall be covered to prevent rainwater intrusion and explosion affecting the service life of the flowmeter;
The flowmeter of gas turbine flowmeter can be installed horizontally or vertically. The flow direction of the fluid shall be consistent with the direction marked on the shell. There shall be a straight pipe section of no less than 10dn at the upstream of the flowmeter and no less than 5dn at the back of the meter.
In order not to affect the normal transmission of the fluid, it is recommended to install a bypass line, which must be closed in normal use.
Suggestions for pipeline construction: during pipeline construction, expansion pipe or bellows shall be installed to avoid serious stretching or fracture of gas turbine flowmeter; the connection between pipeline and gas turbine flowmeter inlet and outlet shall be coaxial, and gasket and weld shall be prevented from penetrating into the pipeline, otherwise the flow profile will be disordered;
When using external power supply, the gas turbine flowmeter must be reliably grounded, but it is not allowed to share the ground wire with the strong current system;
During the installation or maintenance of the pipeline, the ground wire of the electric welding system shall not be overlapped with the flowmeter;
When the pipeline is installed for sealing pressure test, pay attention to the pressure that the pressure sensor of gas turbine flowmeter can bear (i.e. the medium pressure on the verification certificate), so as not to damage the pressure sensor.