Type 2 AC surge protector
-
Imax: 10kA/20kA/40kA/60kA
-
MOV technology
-
Pluggable module for each phase
-
Remote signaling (option)
-
IEC 61643-11 / EN 61643-11 compliant
The working principle of surge protection device:
The surge arresters commonly defined as SPDs (Surge Protection Devices), are devices designed to protect electric systems and equipment against transient and impulse overvoltages such as those caused by lightning strikes and by electric switching.
Their function is to divert the discharge or impulse current generated by an overvoltage to earth/ground, thereby protecting the equipment downstream.
SPDs are installed in parallel with the electric line to be protected. At the mains rated voltage, they are comparable to an open circuit and have a high impedance at their ends.
In the presence of an overvoltage, this impedance falls to very low values, closing the circuit to earth/ground.
Once the overvoltage has ended, their impedance rises again rapidly to the initial value (very high), returning to open loop conditions.
The Type 2 SPD is the main protection system for all low voltage electrical installations. Installed in each electrical switchboard, it prevents the spread of overvoltages in the electrical installations and protects the loads.
Type 2 surge protective devices (SPDs) are designed to protect electric installations and sensitive equipment against indirect surges and ensuring a low protection level (Up).
Type 2 surge protective devices provide effective protection against these dynamic disturbance variables. Whether in an industrial environment or in a residential building, type 2 protection ensures basic protection for your installations and devices.
The TRS4 series type 2 SPDs are available have a discharge capacity of 10kA, 20KA, 40KA, 60KA in single-phase or 3-phase configuration and with various voltages in order to protect any type of power supply system.
THOR Type 2 DIN-rail SPD features are offering quick thermal response and perfect cut-off function and providing fast and reliable protection for various power supply systems.And its capacity to safely discharge current with 8/20 μs waveform.
Built with window fault indication and optional remote alarm contact, it can monitor the operating status of the SPD itself.
TRS4-D10 TRS4-D20 TRS4-C40 TRS4-B60
- Electrical Characteristics
Typ name
TRS4-D10
SPD type
T2
Max. continuous operating ac. voltage (50 / 60 Hz) (Uc)
275V
Voltage protective level(Up) (kv)
≤0.9
Nominal discharge current (8/20μs) (In)
5kA
Max. discharge current (8/20μs) (Imax)
10kA
Max impulse current(10/350μs)Iimp(kA)
---
Residual Current
None
Follow current
None
Other Max.voaltge can be option
320v,385v,420v,440v....
- Mechanical Characteristics
Technology
MOV
SPD configuration
1pole,2pole,3pole,4pole
Connection to Network
by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Din rail 35 mm
Housing material
Flame retardant plastic
Working temperature
-40℃-- +70℃
Degree of protection
IP20
Response time
<25ns
Indication of invalidation
Normal: green; invalidation: red.
Remote of signalling
can be option if need
Dimension
see diagram
- Electrical Characteristics
Typ name
TRS4-D20
SPD type
T2
Max. continuous operating ac. voltage (50 / 60 Hz) (Uc)
275V
Voltage protective level(Up) (kv)
≤1.0
Nominal discharge current (8/20μs) (In)
10kA
Max. discharge current (8/20μs) (Imax)
20kA
Max impulse current(10/350μs)Iimp(kA)
---
Residual Current
None
Follow current
None
Other Max.voaltge can be option
320v,385v,420v,440v....
- Mechanical Characteristics
Technology
MOV
SPD configuration
1pole,2pole,3pole,4pole
Connection to Network
by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Din rail 35 mm
Housing material
Flame retardant plastic
Working temperature
-40℃-- +70℃
Degree of protection
IP20
Response time
<25ns
Indication of invalidation
Normal: green; invalidation: red.
Remote of signalling
can be option if need
Dimension
see diagram
- Electrical Characteristics
Typ name
TRS4-C40
SPD type
T2
Max. continuous operating ac. voltage (50 / 60 Hz) (Uc)
275V
Voltage protective level(Up) (kv)
≤1.3
Nominal discharge current (8/20μs) (In)
20kA
Max. discharge current (8/20μs) (Imax)
40kA
Max impulse current(10/350μs)Iimp(kA)
---
Residual Current
None
Follow current
None
Other Max.voaltge can be option
320v,385v,420v,440v....
- Mechanical Characteristics
Technology
MOV
SPD configuration
1pole,2pole,3pole,4pole
Connection to Network
by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Din rail 35 mm
Housing material
Flame retardant plastic
Working temperature
-40℃-- +70℃
Degree of protection
IP20
Response time
<25ns
Indication of invalidation
Normal: green; invalidation: red.
Remote of signalling
can be option if need
Dimension
see diagram
- Electrical Characteristics
Typ name
TRS4-B60
SPD type
T2
Max. continuous operating ac. voltage (50 / 60 Hz) (Uc)
275V
Voltage protective level(Up) (kv)
≤1.5
Nominal discharge current (8/20μs) (In)
30kA
Max. discharge current (8/20μs) (Imax)
60kA
Max impulse current(10/350μs)Iimp(kA)
---
Residual Current
None
Follow current
None
Other Max.voaltge can be option
320v,385v,420v,440v....
- Mechanical Characteristics
Technology
MOV
SPD configuration
1pole,2pole,3pole,4pole
Connection to Network
by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Din rail 35 mm
Housing material
Flame retardant plastic
Working temperature
-40℃-- +70℃
Degree of protection
IP20
Response time
<25ns
Indication of invalidation
Normal: green; invalidation: red.
Remote of signalling
can be option if need
Dimension
see diagram