It is used for power transmission on power lines of rated voltage 0.6/1kV or lower. It is widely used in petrochemical industry, metallurgy, mines and high-rise buildings.
STANDARD:
IEC 60502-1
MAIN FEATURES:
1) Cable main conductor has low and even proper (inverse order) and zero order impedance, which benefits quality improvement for power supply.
2) Concentric conductor has the lower zero preface resistance. This benefits the sensitive action of automatic protection devices in short circuit and ensures safe operation of cable and concerned devices.
3) Cable has strong resistant characters against electromagnetic interference and thunder strike.
WORKING CONDITION:
1) The tallest work temperature of the cable conductor: PVC insulation is 700C. XLPE insulation is 900C.
2) Short-circuit time (Continuously time is not over the 5s), The temperature of the conductor do not exceed: PVC insulation is 1600C. XLPE insulation is 2500C.
3) The minimum bent radius of the cable: Single core is 20D, Many core 15D.
SPECIFICATION:
SPECIFICATION
DIAMETER OF CONDUCTORES
OVERALL DIAMETER
APPROX. WEIGHT
DC RESISTANCE
CENTRAL
CONCENTRICO
INSULATION THICKNESS
SHEATH THICKNESS
N° HILOS
DIAMETRO
Nº x mm²
mm
mm
mm
mm
mm
Kg/Km
Ω/km
2 x 6
2.71
27
0.55
0.8
1.4
9.3
101
4.61
2 x 10
3.51
25
0.7
0.8
1.4
10.4
130
3.08
2 x 16
4.87
21
0.98
0.8
1.4
12.1
179
1.91
2 x 25
6.42
24
1.15
0.8
1.4
14
249
1.20
3 x 10
3.51
49
0.55
0.8
1.6
18
688
3.08
3 x 16
4.87
52
0.62
0.8
1.6
20.3
813
1.91
4 x 10
3.51
53
0.55
0.8
1.6
18.9
752
3.08
4 x 16
4.87
65
0.56
0.8
1.6
21.3
900
1.91
APPLICATION:
It is used for power transmission on power lines of rated voltage 0.6/1kV or lower. It is widely used in petrochemical industry, metallurgy, mines and high-rise buildings.
STANDARD:
IEC 60502-1
MAIN FEATURES:
1) Cable main conductor has low and even proper (inverse order) and zero order impedance, which benefits quality improvement for power supply.
2) Concentric conductor has the lower zero preface resistance. This benefits the sensitive action of automatic protection devices in short circuit and ensures safe operation of cable and concerned devices.
3) Cable has strong resistant characters against electromagnetic interference and thunder strike.
WORKING CONDITION:
1) The tallest work temperature of the cable conductor: PVC insulation is 700C. XLPE insulation is 900C.
2) Short-circuit time (Continuously time is not over the 5s), The temperature of the conductor do not exceed: PVC insulation is 1600C. XLPE insulation is 2500C.
3) The minimum bent radius of the cable: Single core is 20D, Many core 15D.