GCS AC low voltage distribution cabinet

Model
Nature of the Manufacturer
Other
Product Category
Low voltage switch cabinet
Place of Origin
City, Province
Overview
Normal operating conditions■ the ambient air temperature shall not be higher than + 40 ℃ and not lower than - 5 ℃, and the average temperature within 24 hours shall not be higher than + 35 ℃.■ atmospheric conditions: the air is clean and the relative humidity does not exceed 50% at the maximum temperature of + 40 ℃. Higher relative humidity is allowed at lower temperature, such as 90% at + 20 ℃. It should be considered that moderate condensation may occur occasionally due to temperature changes.■ altitude shall not......
Product Details

Normal operating conditions

■ the ambient air temperature shall not be higher than + 40 ℃ and not lower than - 5 ℃, and the average temperature within 24 hours shall not be higher than + 35 ℃.

■ atmospheric conditions: the air is clean and the relative humidity does not exceed 50% at the maximum temperature of + 40 ℃. Higher relative humidity is allowed at lower temperature, such as 90% at + 20 ℃. It should be considered that moderate condensation may occur occasionally due to temperature changes.

■ altitude shall not exceed 2000m.

■ pollution level 3.

■ the equipment is applicable to the transportation and storage process of the following temperatures: - 25 ℃ to + 55 ℃, up to + 70 ℃ in a short time (no more than 24h). Under these extreme temperatures, the equipment shall not suffer any irreparable damage, and shall be able to work normally under normal conditions.

■ if the above service conditions cannot be met, it shall be settled through negotiation between the user and the manufacturer.

Functional unit:

■ the module of drawer layer height is 160mm. It is divided into five size series: 1 / 2 unit, 1 unit, 1.5 unit, 2 unit and 3 unit.

■ rated current of unit circuit is 400A and below (maximum current of economical unit circuit is 630A).

■ the drawer changes only in height, and its width and depth remain unchanged. Drawers with the same functional units have good interchangeability. One drawer or two MCC units of each drawer can be installed at most.

■ the operating mechanism on the drawer panel has obvious signs of opening, closing, test, extraction and other positions.