36kV outdoor HV porcelain type vacuum circuit breaker with IEC 62271 standard. It is designed as a AC three-phase 50Hz and rated voltage 36kV equipment that is mainly applied to rural and urban power grids with 36kV distribution system for the use of opening and closing of load current, overload current and short circuit current.
36kV outdoor HV vacuum circuit breaker is designed as a AC three-phase 50Hz and rated voltage 36kV equipment that is mainly applied to rural and urban substation power grids with 36kV distribution system for the use of opening and closing of load current, overload current and short circuit current. The outdoor adopts porcelain as insulation material which has advantages of anti-condensation, aging resistance and temperature resistance.
Features of the outdoor 36kV vacuum circuit breaker :
It is suitable for column installation or substation applications. The insulation material is porcelain. Vacuum arc-extinguishing chamber, insulating rod, connecting rod and three-pole epoxy pillar are mounted in mechanism casing. The moving end of arc-extinguishing chamber is connected to the output shaft of the mechanism through insulatiing rod.
Waterproof box design and heater design which prevent the control room from moisture.
High reliability, small volume, long service life.
Comply with IEC 62271-100 standard.
Use of the environment:
Ambient temperature: -40 ℃~ +85 ℃, the daily average temperature: 25 ℃
Altitude: ≤3000m(in excess of the value of technical discussions with the Division I)
Wind speed:35m/ s
Icing thickness: 10mm
Earthquake intensity: ≤8 degrees
Degree of ambient air contamination level not greater than: Ⅲ level
Daily average ambient air relative humidity ≤ 95%, on average ≤ 90%
Saturated vapor pressure of daily mean values ≤ 2.2 × 10-3Mpa, on average ≤ 1.8 × 10-3Mpa
Circuit-breaker on Column | | RVB-24 | RVB-36 | RVB-40.5 |
Standard | IEC 62271-100 | √ | √ | √ |
Rated voltage | (kV) | 24 | 36 | 40.5 |
Rated insulation voltage | (kV) | 24 | 36 | 40.5 |
Power frequency withstand | (kV /min) | 70 (dry) / 70 (wet) | 95 (dry) / 95 (wet) | 95 (dry) / 95 (wet) |
Impulse withstand voltage | (kV peak) | 170 | 170 | 195 |
Rated frequency | (Hz) | 50-60 | 50-60 | 50-60 |
Rated normal current | (Amps) | 2500 | 2500 | |
Rated symmetrical breaking capacity | (kA r.m.s) | 25 25 31.5 | 25 25 31.5 | 31.5 31.5 |
Rated short time withstand current (3s) | (kA r.m.s) | 25 25 31.5 | 25 25 31.5 | 31.5 31.5 |
Asymmetrical breaking capacity | (% of d.c Component at t=45ms) | 35 | 35 | 35 |
Rated making capacity | (kA peak) | 63 63 80 | 63 63 80 | 80 80 |
Operating sequence | 0-0.3sec- CO - 3 Min -CO & CO-15sec- CO | √ | √ | √ |
Opening time | (ms) | 45 ± 10 | 45 ± 10 | 45 ± 10 |
Capacitor current switching capacity | (Amps) | | | |
Single bank - C2 class | 400 | 400 | |
Back to back - C2 class | | | 750 |
Arcing time | (ms) | 5-15 | 5-15 | 5-15 |
Total breaking time | (ms) | 50-60 | 50-60 | 50-60 |
Closing time | (ms) | 75 ± 10 | 75 ± 10 | 75 ± 10 |
Over all dimensions | On Frame (H x L x P) mm | (3090-3840) x 900 x 686 |
Weight | (kg) | 850/900 | 850/900 | 900 |
N2 gas absolute pressure | (kPa) for Anticondensation | 150 | 150 | 150 |
Operating temperature #1 | ℃ | -25…+40 | -25…+40 | -25…+40 |
Tropicalization | IEC:60068-2-30,721-2-1 | √ | √ | √ |
Electromagnetic compatibility | IEC 62271-1,61000-6-2,61000-6-4 | √ | √ | √ |
Solar radiation | (W/m2) | 1000 | 1000 | 1000 |
Presence of pollution | IEC 60815-Table 1 | Level III | Level III | Level III |
Creepage distance | (mm/kV) | 25 #2 | 25 #2 | 27.5 #2 |
Ice coating | (mm) | 10 |
Wind speed | (m/s) | 34 |
Earth quake resistance | (g) | 0.6 |
Surface force on the terminal | Logitudinal xTransversal x Vertical ( N) | 750 x 500 x 750 |