The assembled shunt capacitor is mainly used for 110kV, 66kV and 35kV side of main transformer in areas with limited floor space or high seismic requirements.
The assembled shunt capacitor is mainly used for 110kV, 66kV and 35kV side of main transformer in areas with limited floor space or high seismic requirements, and reactive power compensation for power frequency power system, so as to improve power grid power factor, reduce line loss, give full play to the efficiency of power supply and distribution, and improve the quality of power supply voltage. It has the advantages of good seismic performance, small floor space, easy installation and maintenance, etc.
The main features
1. Adopt the inner unit of the new assembling capacitor, which is safe and reliable in quality.
2. Compact structure, large capacity and small floor space.
3. Multi-insulation platform classification design, the product explosion resistance level is greatly improved.
4. The capacitor body is designed with a terminal box with a signal collector, which is used to collect the voltage, current, temperature, pressure, gas and other signals in the running process of the capacitor to facilitate the monitoring of the running state.
5. The core is made of high-quality new insulation materials and spot-like insulation structure, which can not only ensure good internal insulation performance, but also ensure smooth heat dissipation of the core, making the operation more safe and reliable.
6. The main components adopt bolt and detachable structure, which is not only convenient for installation and transportation, but also convenient for on-site maintenance.
Conditions of use
1. Altitude: ≤1000m.Over 1000m plateau area, the company can be provided with the plateau type of integrated shunt capacitor.
2. Ambient temperature category: -40/B.
3. Pollution level: Level IV.
4. Installation location: outdoors.It can also be used indoors or in areas requiring a small footprint
5. Surrounding environment: no seriously corrosive gases and vapors to the metal, no conductive or explosive dust, and no violent mechanical vibration.
6. When the capacitor is in operation, the remaining voltage at its terminals shall not exceed 10% of the rated voltage.
1. Rated frequency: 50Hz
2. Rated voltage: 20kV, 35kV, 66kV, 110kV
3. Rated Capacity:
35kV voltage class: three-phase integration 10000kVAR, single-phase 3334, 6667, 10000, 20000kVAR
66kV voltage class: single-phase 20000kVAR
110kV voltage class: single-phase 80000kVAR
4. Phase number: three-phase or single-phase
5. Tangent of loss Angle: tangent is not greater than 0.0005
6. Capacitance deviation: the measured capacitance deviation from its rated value shall not exceed 0~+5%, and the ratio of maximum value to minimum value between any two-line terminals of the three-phase capacitor shall not exceed 1.02
7. The capacitor can operate continuously at 1.1 times the rated voltage
8. The capacitor can operate continuously when the overcurrent does not exceed 1.3 times of its rated current
9. Outlet bushing crawl distance: ≥35mm/kV
10. Casing contamination level: Grade D