RVB Outdoor Single Phase Vacuum Circuit Breaker manufactured by Rockwill in China.
Outdoor Single Phase Vacuum Circuit Breaker
Summary
ROCKWILL ® have developed the RVB series of outdoor vacuum circuit breakers using modern processing technology and computer-aided design techniques, combined with the latest generation insulation technology and compact design make whole product light and save volume. RVB ordinary outdoor vacuum circuit breakers, spring actuator comes standard with a mechanical design life of 20,000 times. The RVB(S) series automatic circuit reclosers integrates the functions of control, protection measurement,communication, fault detection, on-line monitoring of closing or opening.
standard
ROCKWILL all series switches meet the following criteria:
ANSI/IEEE C37.60/IEC 62271-100
(GB1984-2003 China standard)
GBT11022-1999 China Standard
IEC 60255-11
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-21-3 Class I
IEC 60255-22-1 Class III
IEC 60255-22-2 Class IV
IEC 60255-22-3 Class III
IEC 60255-22-4 Class IV

10,000 times mechanical life spring mechanism,provide with voltage options:DC and AC 110/220V for opening and trip coils.DC and AC 110/200V for motor and auxiliary heater or temperature and humidity control.

Primary busbar terminal direct connected bolted with the interrupter to reduce unnecessary power losses Vacuum interrupter (APG process using solid-solid insulating sealing technology, plus silicone rubber molding compound technology to improve the overall switch environmental performance) Extensible outlet bushing (plus modular design, which will help increasing insulation margin of creepage distance from further requirements)
RVB series vacuum Circuit Breaker rejection of the traditional switch design concepts, will absorb some of the advanced design concepts, simplifying the overall transmission mode switch, greatly reducing the transmission power loss of this switch makes switching better overall performance and longer life. Makes the whole body switches provide a higher life expectancy, more stable mechanical properties.RVB provides up to 10,000 mechanical operations 5,000 maintenance-free operations.
●Ambient temperature: -40 ℃ ~ +85 ℃, the daily average temperature: 25 ℃; Altitude: ≤ 3000m (inexcess of the value of technical discussions with the Division I); Wind speed: 35m / s;
●Earthquake intensity: not more than 8 degrees;
●Daily average ambient air relative humidity ≤ 95%, on average ≤ 90%;
●Saturated vapor pressure of daily mean values ≤ 2.2 × 10-3Mpa, on average ≤ 1.8 × 10-3Mpa; For
●Unusual environmental conditions, please consult with the manufacturer.
N | Item | Unit | Data |
1 | Rated voltage | kV | 27.5/31.5 |
2 | Rated current | A | 1250/1600/2000/2500 |
3 | Rated capacitor bank breaking current | A | 400/600/800 |
4 | Rated frequency | Hz | 50/60 |
5 | Power frequency 1 min | Dry | kV | 110 |
Wet | 95 |
6 | Lightning impulse withstand voltage(peak) | KV | 185/200 |
7 | Rated short circuit breaking current | KA | 25/31.5 |
8 | Rated Full Fault Breaking Duty | times | 30 |
9 | Rated making current | KA | 63/80 |
10 | Rated short current switching current(peak) | KA | 63/80 |
11 | Rated peak value withstand current | KA | 63/80 |
12 | 4s short time withstand current | KA | 25/31.5 |
13 | Rated operate sequence | | O-0.3S-CO-180s-CO |
14 | Mechanism life | times | 20000 |
15 | Complete breaking time | ms | ≤100 |
16 | Opening time | Highest operate voltage | ms | 15~50 |
Rated operate voltage | ms | 15~50 |
Lowest operate voltage | ms | 30~60 |
17 | Closing time | ms | 25~50 |
18 | Contact closing bounce time | ms | ≤3 |
19 | Out of simultaneity of contact switching | ms | ≤2 |
20 | Contact overtravel on Opening | mm | ≤2 |
21 | Weight | kg | ≤250kg |