RSW type pole mounted vacuum sectionalizer. It applies up to 24KV,400/630A, 50Hz/60Hz.
RSW type pole mounted vacuum sectionalizer
RSW type Pole-mounted load-break switch(Pole-LBS) applies up to 24KV,400/630A, 50Hz pole-LBS associated with a state-of- the-art controller.
This SF6 gas-insulated switch can be corporated with the distribution automation system, and also isolate section of distribution line from the control center.
It is a simple pole-mounting arrangement contribute to quick and low cost installation, and the switch can be operated manually with a electronic controller. Electronic controller is contained in a stainless steel cabinet for an all weather environmental conditions. Remote monitoring and control can also be provided mounting wire or wireless modem in a cabinet.
RSW type vacuum load break switch can be combined with CT/PT and smart controller for achieving a smart sectionalizer, which is muti-function load break switch with senior relay protection and communication.
----------------------------------------------------
Service environment:
a)Air temperature: Maximum temperature:+85℃; Minimum temperature:-45℃.
b)Humidity:Monthlu average humidity 95%; Daily average humidity 90%.
c)Altitude above sea level: Maximum installation altitude:2500m or higher.
d)Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
e)No frequent violent shake.
-------------------------------------------------------
More information pls contact us.
Descriptions | Rating |
Rated voltage | 12KV/24KV |
Rated current | 630A |
Rated frequency | 50Hz |
Rated short-time current | 20KA(r.m.s),4 sec. |
Rated making current | 50KA(peak),3 times |
Load current breaking | 400/630A, 30 times |
Cable charging current breaking | 25A, 10times |
Line charging current breaking | 1.5A, 10 times |
Magnetic current breaking | 22A, 10 times |
Main contact No voltage breaking Ground contact | 5000 times 2000 times |
Closing time Operating timings Opening time | <1.0 sec. <1.0 sec. |
Dry condition, 1minute Power-frequency withstand voltage Wet condition, 10sec. | 50KV/60KV 34KV/50KV |
Impulse withstand voltage(1.2*50us) | 95kV/145kV |
Rated voltage Controller Power frequency withstand voltage Impulse withstand voltgae(1.2*50us) | 220V |
2KV rms,minute |
6KV peak |
|