Pole mounted solid load break switch

Model
Nature of the Manufacturer
Other
Product Category
The Outdoor Switchgear
Place of Origin
City, Province
Overview
RLW type soild type load break switch is a solid dielectric type with silicone rubber coating outdoor switchgear, which is adopt vacuum interrupting technology, equipped with a spring mechanism.
Product Details

RLW type Solid dielectric load break switch

RLW type soild type load break switch is a solid dielectric type with silicone rubber coating outdoor switchgear, which is adopt vacuum interrupting technology, equipped with a spring mechanism.

RLW type load break switch is compact design, very light and easy for pole mounted.

RLW is long mechnical & Electrical design life LBS, It is reliable at 10,000 times operation life.

RLW current rating up to 1250A maximum, 20kA.

RLW type offer the voltage rating : 12kV, 24kV, 36kV

RLW type LBS is also capable to expanding to different functions:

----------------------------------------------------------

Simple function using RLW basic type manual LBS.

Simple function RLW basic type motorized LBS.

----------------------------------------------------------

Multi-function RLW type motorized LBS with CT/PT combination switchgear which can ahieve remote control with normal switching on/off and measuring function.

----------------------------------------------------------

Multi-function RLW type motorized LBS with CT/PT combination switchgear which can ahieve remote control with special sectionalizer functiion.

----------------------------------------------------------

More details information, pls contact us.

 

No.ItemUnitData
1Rated voltagekV12152738
2Rated current at MaxA125012501250800
3Rated frequencyHz50/60
4Power frequency 1minDry
kV
34385070
Wet45506580
5Lightning impulse withstand voltage(peak value)alternate,
opposite/fracture
kV7595/110125/150150/170
6Rated short circuit breaking current at 50 timesA9000900090004500
7Rated short circuit withstand currentkA12.58
8Short time duration timeS3S
9Rating making currentkA4020
10Rated peak value withstand currentkA4020
11Rated operating circulate O-0.3S-CO-15S-CO
12Mechanical life (Design)times10,000
13Mechanical life (free maintenance )2000
14Electrical life   (free maintenance )2000