Outdoor / Indoor Load break switch for MV distribution line
- According to IEC62271-103 standard, Load break switch is a Indoor or Outdoor installation, three/single-phase, alternating current switches and switch disconnectors for their switching function, having small making and breaking current ratings, The rated voltages from 1kV up to 52kV at rated frequency 50/60 Hz.
- A Load break switch i.e switch disconnector with widely using in MV distribution line, with different insulation medium: SF6 gas, Soild, Oil, Air,etc.. and different extinguishing medium: SF6 gas, Air, Vacuum.
Rockwill is offering varity load break switch >>>>
For indoor installation using: RLS type Indoor SF6 Gas load break switch, SF6 Fuse - Switch disconnector, Solid insulation type vacuum load break switch, Air type load break switch. Voltage rating from 6kV up to 40.5kV.
For outdoor installation using: RPS type SF6 Gas load break switch, RTS air type Fuse - Switch disconnector, RLW type Solid insulation type vacuum load break switch, RTS Air type load break switch, etc.
RPS is an SF6-insulated, outdoor pole mounted load break switch family for overhead lines and specifically designed for use in modern remote controlled distribution automation systems.
The RPS offers reliable maintenance free operation even in the most demanding climatic conditions including salt laden atmospheres, corrosive industrial pollution, snow and ice.
It has excellent load breaking and fault making capacity and satisfies the isolation requirements specified for load break switch. The earthed metal tank prevents all possible leakage currents across an open switch. RPS can be manually operated or motor operated for local and remote electric control, upgraded.
More iformation pls consult with us for catalog.
● Summary
ROCKWILL® Electric strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.
RPS is an SF6-insulated, outdoor pole mounted load break switch family for overhead lines and specifically designed for use in modern remote controlled distribution automation systems. The RPS offers reliable maintenance free operation even in the most demanding climatic conditions including salt laden atmospheres, corrosive industrial pollution, snow and ice. It has excellent load breaking and fault making capacity and satisfies the isolation requirements specified for load break switch. The earthed metal tank prevents all possible leakage currents across an open switch. RPS can be manually operated or motor operated for local and remote electric control, upgraded.
● Service environment
1.Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
Humidity: Monthly average humidity 95%; Daily average humidity 90% .
Altitude above sea level: Maximum installation altitude: 2500m or more higher.
Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake
●Offering
With optional classes for rated current range:
--Type RPS 15, Rating6-20 kV with 400A, 16 kA up to 1250A, 20kA;
--Type RPS 27, Rating22-27 kV with 400A, 16 kA up to 1250A, 20kA;
--Type RPS 38, Rating30-40.5 kV with 400A, 16 kA up to 1250A, 20kA;
With optional classes for different grid application installation:
Section function (Section)
50 Instantaneous/Definite-Time Overcurrent(P.OC)
51 Phase Time-Overcurrent(P.Fast curve/P.Delay curve)
Overload (N.Fast curve/N.Delay curve)
50N Residual Ground Instantaneous/Definite-Time Overcurrent(G.OC)
51N Residual Ground Time-Overcurrent (G.Fast curve/G.Delay curve)
50SEF Sensitive Earth Fault (SEF)
51c Cold Load(Cold load)
TRSOTF Switch-Onto-Fault(SOTF)
59 Over Voltage(L.Over volt)
27 Under Voltage (L.Under volt)
Monitoring Functions:
Primary/Secondary Phases and Earth Currents
Direction
Primary/Secondary Line and Phase Voltages
Apparent Power and Power Factor
Real and Reactive Power
Historical Demand Record
Positive Phase Sequence Voltage & Current
Negative Phase Sequence Voltage & Current
Zero Phase Sequence Voltage
Frequency
Binary Input/Output status
Trip circuit healthy/failure
Time and date
Fault records
Event records

●Time-Overcurrent Curves
The following information describes the curve timing for the curve and time dial settings made for the time-overcurrent elements The time-overcurrent relay curves in conform to IEEE C37.112-1996 IEEE Standard Inverse-Time Characteristic Equations for Overcurrent Relays.
IEC Curves: |
 | C1 (Standard Inverse) C2 (Very Inverse) C3 (Extremely Inverse) C4 (Long-Time Inverse) C5 (Short-Time Inverse) |
U.S. Curves: |
 | U1 (Moderately Inverse) U2 (Inverse) U3 (Very Inverse) U4 (Extremely Inverse) U5 (Short-Time Inverse) |
● PC software for controller Testing, Setting, programing, Update.

Human friendship interface Programmable Time-Overcurrent curve

● RPS feature
The high quality 3 mm stainless steel are used for tank, which is designed for its maximum robustness and minimum welding line to minimize corrosion, and specifically to guarantee the safety of the operation personnel even with the internal arc faults at the maximum fault capacity of the tank the RPS can withstands an internal fault without venting hot gases.
The independent spring operation mechanism adopt ROCKWILL® patent spiral spring, provides a guaranteed load break fault make capability by ensuring the opening and closing speed of the switch.
The RPS is provided with light reflecting position indicator which are directly connected to the switch operating shaft providing clear and unambiguous switch position indication. Indicator made of light reflecting material, which is easily visible from ground level even at night in driving rain.
● Main new advantages of RPS
ROCKWILL® Supply special design manual closing device technology with own patent, It applied for normal and abnormal situation closing. It’s closing speed(time) comply with IEC62271-100.
This function can offset from magnetic actuator fault which when actuator can’t work will cause the major accident.
Corrosion resistant, Composite bushingManual lock-out mechanism (including hook stick) Reliable housing groundO/C indicator (made of light reflecting material), Operation counter, Gas density gauge which are easily visible from ground level.
Advanced and Integrated helium leakage detecting and filling equipment, which ensuring SF6 leakage of each switch is less than 0.1% strictly per year.
Motor drive, which easily retrofitted on site to manually operated units.

● Creepage Distances of RPS
Terminal to ground creepage | 15kV BIL 95/110kV | 27kV BIL125/150kV | 38kV BIL 170/200kV |
Composite bushing | 564mm | 840mm | 1400mm |
Porcelain bushing | 556mm | 708mm | 1250mm |
●Current transformer and Voltage sensor
Part Number | RPS-15 | RPS-27 | RPS-38 |
Manual | Motorize | Manual | Motorize | Manual | Motorize |
Current transformer | / | 3 | / | 3 | / | 3 |
Voltage sensor | / | 3/6 | / | 3/6 | / | 3/6 |
Note: Current transformers and voltage sensors can be customized according to requirements.
●Standards for reference
IEC 62271-1 IEC 62271-102 IEC 62271-103
High-voltage switchgear and controlgear. Part 103: switches for rated voltage above 1 kV up to and including 52 kV

Front: Color clear O/C indicator Rear:Highly reliable explosion-proof valve,Inflatable/deflation integrated device