38kV Auto Recloser

Model
Nature of the Manufacturer
Other
Product Category
The Outdoor Switchgear
Place of Origin
City, Province
Overview
38kV type RCW+ type auto circuit recloser is designed for using system voltage rating up to maximum 42kV, BIL 200kV. It is high quality class auto recloser, with maximum 6 voltage sensors and it is high precision and wide range of measuring for current and voltage.
Product Details

38kV Auto Circuit Recloser - Rockwill Brand

Rcw+ type 38kV auto circuit recloser is designed for using voltage rating up to maximum 42kV level system. In order to provide with a high reliable equipments, Rockwill's team increased the whole design schemas as below.

---------------------------------------------------

Rcw+ type 38kV auto circuit recloser is ANSI/IEC standardized plus design products which is equipped with one magnetic actuator mechanism, one manual device for closing, opening and locking, 3 current sensors, max 6 voltage sensors, with more functional like protection curves + curves programble, coodination logics + logics  programble,  programble communication protocols, PC software, APP control tool, etc...  with RWK352 controller,....

---------------------------------------------------

Rcw+ type 38kV auto circuit recloser is a solid insulation reclosure with zero pressure Sf6 GAS sealed. with high creepage design, higher insulation level,  suit using for Maximum 42kV level sytem. It's vacuum interrupting technology, and IP67 IP protection class, It avoid any bad influence high polution enviroment of humidity, salt or alkali incursion or small animal,etc...

---------------------------------------------------

Rcw+ type 38kV auto circuit recloser is proper for using in either important area or extreme bad envirment area which normal ACR is not capable well service!

● Service environment

Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃

Humidity: Monthly average humidity 95%; Daily average humidity 90% .

Altitude above sea level: Maximum installation altitude: 2500m or more higher.

Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake

●Offering With optional classes for rated current range:

--Type RCW38, Rating30-40.5 kV with 630A, 16 kA up to 800A, 20kA;

With optional classes for different grid application installation: Single phase & Three phase.

With optional relay protection& logics for user choice:

+Instantaneous over-current protection.

+Timing over-current protection

+Negative sequence over-current protection.

+Directional over-current protection(*).

+Over-voltage protection./Under voltage protection.

+Programable protection relay curves total 10 nos ANSI/IEC curves.

+Cold load pickup protection TCC +Hot line tag

+Earth protection EF/SEF +Zone Sequence Co-ordination

+More relay functions can be customized.

With optional communication protocols & I/O port for user choice:

38kV auto circuit recloser controller

RS-232 and RS-485 ports supporting.

DNP3.0 communication protocol support(*).

Modbus communication protocol is optional(*).

IEC 60870-5-101 communication protocol support.

IEC 60870-5-104 communication protocol support.(*).

IEC 61850 communication protocol support.(*).

The recloser can communicate through GPRS(Or GSM) modem with English or Specified language (*).

With optional functions for user.

Rated currents, System phase current.

Rated voltages, System phase voltage& secondary low voltage power supply voltage. Frequency, power(kWh),

reactive power(kV arh), power factor .

With optional reclosing interval for user pre-program:

Reclosing times setting support.

Dead time setting support.

With events recording function:

SOE 10000 operations record.

Fault record and normal operation record.

Note: (*) mean should customized by manufacturer if needed.

●Time-Overcurrent Curves The following information describes the curve timing for the curve and time dial settings made for the time-overcurrent

elements The time-overcurrent relay curves in conform to IEEE C37.112-1996 IEEE Standard Inverse-Time

Characteristic Equations for Overcurrent Relays.

IEC Curves: 
38kV auto recloser programble curveC1 (Standard Inverse)
C2 (Very Inverse)
C3 (Extremely Inverse)
C4 (Long-Time Inverse)
C5 (Short-Time Inverse)
U.S. Curves: 
38kV auto recloser programble ANSI curveU1 (Moderately Inverse)
U2 (Inverse)
U3 (Very Inverse)
U4 (Extremely Inverse)
U5 (Short-Time Inverse)

● PC software for controller Testing, Setting, programing, Update.

38kV auto recloser pc software

Human friendship interface                                               Programmable Time-Overcurrent curve

38kV vacuum recloser testing software

 

● Recloser feature a)Outline of recloser:

The RCW series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.

b)The recloser tank feature:

The Vacuum recloser tanks are manufactured from 304# grade stainless steel and are powder coated a light grey colour. Whole recloser IP67 protection class, equipped with a auxiliary plug to connect with recloser controller by control cable, Diameter Max22mm, 6 M length (8M for special).

It’s can performance serve more than 20 years long term under heavy duty circumstance.

● Main new advantages of RCW

38kV auto recloser tank

 

Visible ON/OFF indicatorIP67 class waterproof plug connector

1.Apply ANSOFT design the high performance magnetic actuator,high reliable and free maintenance
2.Manual closing device
3.Automatic Blocking Device for Manual opening
4.Mechanical locking device
5.Electronic locking device
6.Mechanical counter
7.Electronic counter
8.Visble on the ground reflector material mechanical open/closer indicator
9.IP67 inflatable tank SF6 Gas insulation,Pneumatic value,barometer
10.Integral type tank .Lifting lug, Earthing bolt
Note:The above parts are optional devices.Please provide requirement before placing an orde

 

Primacy incomer terminal (directly connect to interrupter reduce power lost) Current sensor (external modular design easy for quality control and maintenance) Accuracy: ±0.5% Ratio:800/1

38kV auto recloser vacuum pole

Vacuum interrupter(Adopt the APG technology,increasing the whole insulation and weathering performance)
Internal Voltage sensors incorporated within the vacuum interrupter module It's equipped with two voltage sensors,one for measuring the voltage of incoming side,and another one for measuring the voltage of outgoing side.

38kV auto recloser solid pole

shielded 4-conductor cable connection  Accuracy:±0.2% Voltage Sensor  Ratio:500/1 or 1000/1

 

● Creepage Distances of RCW

Description12kV BIL
75/95kV
15kV BIL
95/110kV
27kV
BIL125/150kV
38kV BIL
170/200kV
Terminal to terminal creepage600mm840mm1250mm1380mm
Terminal to ground creepage510mm760mm1200mm1300mm

 

● Main technical data

NItemUnitData
1Rated max voltagekV12152738
2Rated currentA630/800/1250
3Rated frequencyHZ50/60
4Power frequency 1minDrykV45556595
Wet30455580
5Lightning impulse withstand voltage(peak)kV75/95*95/100*125/150*170/200*
6Rated short circuit breaking currentkA12.5/16/20/25*
7Rated short current switching current(peak)kA31.5/40/50/63*
8Rated peak value withstand currentkA31.5/40/50/63*
94S short time withstand currentkA12.5/16/20/25*
11Rated operating circulate O-0.5S-CO-2S-CO-2S-CO
10Breaking current frequency under rated short circuittime200
12Mechanism lifetime10000
13Secondary loop 1 min power frequency withstandkV2
14Auxiliary voltage supplyVac220±20%
15Battery bankVdc12×2
16Capacitor unitVdc220

●Accessories of RCW

All above insulating components for BIL 200kV expanding using. Any question please contact with our engineer.

38kv auto recloser accessories

Upper voltage shield 3 pcs/set

Standard made of T2 copper material, for 630/1250A rated current using. With  expanding range.

38kv auto recloser terminal

Terminal 6 pcs/set

Map guide&location Monitoring&Controlling

38kV auto recloser app software 38kV auto recloser app control software

 

Setting & Modification Event Records

38kV auto recloser app software parameter setting 38kV auto recloser app software event report

 

●Master software for Distribution Automation Management

38kV auto recloser app software map

38kV auto recloser app software SLD