Rockwill Standard Recloser

Model
Nature of the Manufacturer
Other
Product Category
The Outdoor Switchgear
Place of Origin
City, Province
Overview
Rockwill Auto Recloser is a IEC standard intelligent pole mounted switch for using on medium voltage overhead distribution lines. It is also called vacuum recloser, pole mounted recloser or outdoor recloser.
Product Details

What is the standard of Rockwill Auto Recloser?

Rockwill Auto Recloser is a flexible pole mounted outdoor vacuum switching device that can trip and reclose up for a temporary distribution line fault. It reduces the blackout time greatly and improves the stability of power grid operation. The operation status also can be controlled and monitored by phone and SCADA system.

Rockwill standard auto recloser is fully meets the IEC62271-111 & ANSI/IEEE C37.60 standard. Fully follow the above standard for type test and routine test. Additional functions reuirement is offered, like: ESKOM standard, TANESCO standard, BPC standard, SEC standard, DEC, Meralco, KPLC, BREB, etc. Besides, Rockwill even provide with patent design for new recloser.

RCW+ Auto Recloser

RCW+ type auto recloser is ANSI/IEC standardized plus design products which is equipped with one magnetic actuator mechanism, one manual closing/opening/Locking device, 3 current sensors, max 6 voltage sensors, with more functional like protection curves + curves programble, coodination logics + logics  programble, programble communication protocols (Modbus, DNP3.0, IEC 60870-5-101/104), PC software, APP control tool, etc.

RCW+ type automatic circuit recloser is a solid insulation reclosure with zero pressure SF6 gas sealed. It has higher creepage design and higher insulation level for using on Maximum 42kV level sytem. 

It uses vacuum interrupting technology, and meeting IP67 IP protection class, It avoids any bad influence like high polution enviroment of humidity, salt or alkali incursion or small animals.

● Main technical data of auto recloser

NItemUnitData
1Rated max voltagekV12152738
2Rated currentA630/800/1250
3Rated frequencyHZ50/60
4Power frequency 1minDrykV45556595
Wet30455580
5Lightning impulse withstand voltage(peak)kV75/95*95/100*125/150*170/200*
6Rated short circuit breaking currentkA12.5/16/20/25*
7Rated short current switching current(peak)kA31.5/40/50/63*
8Rated peak value withstand currentkA31.5/40/50/63*
94S short time withstand currentkA12.5/16/20/25*
11Rated operating circulate O-0.5S-CO-2S-CO-2S-CO
10Breaking current frequency under rated short circuittime200
12Mechanism lifetime10000
13Secondary loop 1 min power frequency withstandkV2
14Auxiliary voltage supplyVac220±20%
15Battery bankVdc12×2
16Capacitor unitVdc220
Rockwill's recloser gather multi relay protections like:
EF1/EF2SEF1/SEF2Cold Load Pickup
Live Load BlockingOscillography Capture capability
Programmable Logic4 Independent Protection Groups
Advanced AutomationHarmonic Protection and Monitoring
Hot Line Tag CapabilityNegative Phase Sequence Overcurrent
Inverse Time ProtectionLive Line Function & Hot Line Tag Function
Definite Time ProtectionDirectional Sensitive ground Fault Protection
Two fast-two slow curvesPhase (OV1) & Line-to-Line (OV2) Over Voltage
Temporary Time AdditionDirectional over current and ground fault protection
Voltage Protection ElementPhase under-voltage balanced element (UV1)
Logic program-able functionPhase-to-Phase Under-voltage Element (UV2)
Zone Sequence Co-ordinationLoss of Supply (UV3)
High set Instantaneous elementVoltage Sag Protection (UV4 Sag)
Power Quality monitoring including Systems Performance Indices, Voltage Sags and Swells
Voltage reclose control with automatic back feed(restoration provides loop automation functionality)

If you want more functions, pls consult with us!

Part NumberRCW15M/630-20RCW27M/630-20RCW38M/630-20
Current Sensing3 x Current Transformers3 x Current Transformers3 x Current Transformers
Voltage Sensing3 x Voltage Sensors3 x Voltage Sensors3 x Voltage Sensors
Control TypeRWK-351RWK-351RWK-351

● Service environment

Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃

Humidity: Monthly average humidity 95%; Daily average humidity 90% .

Altitude above sea level: Maximum installation altitude: 2500m or more higher.

Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake

●Offering With optional classes for rated current range:

--Type RCW12, Rating 6-12 kV with 630A, 16 kA up to 1250A, 20kA;

--Type RCW15, Rating15-20 kV with 630A, 16 kA up to 1250A, 20kA;

--Type RCW27, Rating22-27 kV with 630A, 16 kA up to 1250A, 20kA;

--Type RCW38, Rating30-40.5 kV with 630A, 16 kA up to 800A, 20kA;

With optional classes for different grid application installation: Single phase & Three phase.

With optional relay protection& logics for user choice:

+Instantaneous over-current protection.

+Timing over-current protection

+Negative sequence over-current protection.

+Directional over-current protection(*).

+Over-voltage protection./Under voltage protection.

+Programable protection relay curves total 10 nos ANSI/IEC curves.

+Cold load pickup protection TCC +Hot line tag

+Earth protection EF/SEF +Zone Sequence Co-ordination

+More relay functions can be customized.

With optional communication protocols & I/O port for user choice:

advanced auto recloser controller

RS-232 and RS-485 ports supporting.

DNP3.0 communication protocol support(*).

Modbus communication protocol is optional(*).

IEC 60870-5-101 communication protocol support.

IEC 60870-5-104 communication protocol support.(*).

IEC 61850 communication protocol support.(*).

The recloser can communicate through GPRS(Or GSM) modem with English or Specified language (*).

With optional functions for user.

Rated currents, System phase current.

Rated voltages, System phase voltage& secondary low voltage power supply voltage. Frequency, power(kWh),

reactive power(kV arh), power factor .

With optional reclosing interval for user pre-program:

Reclosing times setting support.

Dead time setting support.

With events recording function:

SOE 10000 operations record.

Fault record and normal operation record.

Note: (*) mean should customized by manufacturer if needed.

●Time-Overcurrent Curves The following information describes the curve timing for the curve and time dial settings made for the time-overcurrent

elements The time-overcurrent relay curves in conform to IEEE C37.112-1996 IEEE Standard Inverse-Time

Characteristic Equations for Overcurrent Relays.

IEC Curves: 
auto recloser protection IEC curveC1 (Standard Inverse)
C2 (Very Inverse)
C3 (Extremely Inverse)
C4 (Long-Time Inverse)
C5 (Short-Time Inverse)
U.S. Curves: 
auto recloser protection ANSI curveU1 (Moderately Inverse)
U2 (Inverse)
U3 (Very Inverse)
U4 (Extremely Inverse)
U5 (Short-Time Inverse)

● PC software for controller Testing, Setting, programing, Update.

auto recloser parameter setting software

Human friendship interface                                               Programmable Time-Overcurrent curve

auto recloser PC testing software

 

● Recloser feature a)Outline of recloser:

The RCW series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.

b)The recloser tank feature:

The Vacuum recloser tanks are manufactured from 304# grade stainless steel and are powder coated a light grey colour. Whole recloser IP67 protection class, equipped with a auxiliary plug to connect with recloser controller by control cable, Diameter Max22mm, 6 M length (8M for special).

It’s can performance serve more than 20 years long term under heavy duty circumstance.

● Main new advantages of RCW

auto recloser switch tank

 

Visible ON/OFF indicatorIP67 class waterproof plug connector

1.Apply ANSOFT design the high performance magnetic actuator,high reliable and free maintenance
2.Manual closing device
3.Automatic Blocking Device for Manual opening
4.Mechanical locking device
5.Electronic locking device
6.Mechanical counter
7.Electronic counter
8.Visble on the ground reflector material mechanical open/closer indicator
9.IP67 inflatable tank SF6 Gas insulation,Pneumatic value,barometer
10.Integral type tank .Lifting lug, Earthing bolt
Note:The above parts are optional devices.Please provide requirement before placing an orde

 

Primacy incomer terminal (directly connect to interrupter reduce power lost) Current sensor (external modular design easy for quality control and maintenance) Accuracy: ±0.5% Ratio:800/1

solid dielectric auto recloser vacuum pole

Vacuum interrupter(Adopt the APG technology,increasing the whole insulation and weathering performance)
Internal Voltage sensors incorporated within the vacuum interrupter module It's equipped with two voltage sensors,one for measuring the voltage of incoming side,and another one for measuring the voltage of outgoing side.

solid dielectric auto recloser pole

shielded 4-conductor cable connection  Accuracy:±0.2% Voltage Sensor  Ratio:500/1 or 1000/1

 

● Creepage Distances of RCW

Description12kV BIL
75/95kV
15kV BIL
95/110kV
27kV
BIL125/150kV
38kV BIL
170/200kV
Terminal to terminal creepage600mm840mm1250mm1380mm
Terminal to ground creepage510mm760mm1200mm1300mm


●Accessories of RCW

All above insulating components for BIL 200kV expanding using. Any question please contact with our engineer.

Upper voltage shield 3 pcs/set

Standard made of T2 copper material, for 630/1250A rated current using. With  expanding range.

Terminal 6 pcs/set

Map guide&location Monitoring&Controlling

auto recloser  software auto recloser APP management software

 

Setting & Modification Event Records

 

 

●Master software for Distribution Automation Management

The Sternest Warning Before You Operate Recloser!

 

Make Sure That:

1. Please make sure the battery is ready full charged (12 hours) before operating recloser controller!

2. It is not allowed to use emergency opening and closing handle at normal condition!

3. It is not allowed to repeat press the Open/Close button continuously without intermission!

 

Further Warning!

Special attention should be paid to the following points, which may cause the recloser to fail to work.

  1. About Controller parameter setting

▲Do not modify CT rate, PT rate, PTS rate in controller!

▲Do not modify recloser sequence, it is O-0.5s-CO-2s-CO-5s-CO in IEC standard.   

auto recloser CT rate setting auto recloser PT rate setting auto recloser parameter modification

 

  1. About OPEN/CLOSE operation

 ▲It’s not allow to repeat press the Open/Close button continuously without intermission.

 ▲Please contact us in time, frequent operation will burn the controller components

auto recloser controller operation

 

  1. About manual closing device (Yellow handle)

 ▲It is not allowed to do manual closing operation if not necessary emergency demand.

 ▲Make sure the recloser is at OFF position and controller can’t drive it into close situation

 ▲After closing successfully, continue to pull down for 3 times to release the lockout.

 ▲It is only allowed to be used in special non-electric operation situation.

 

The above three points are special remarks, do observe strictly.

 