Outdoor Auto Recloser

Model
Nature of the Manufacturer
Other
Product Category
Vacuum Circuit Breaker
Place of Origin
City, Province
Overview
ZW32 series outdoor high-voltage vacuum circuit breakers are outdoor high-voltage distribution devices with rated voltage of 12KV-36KV and three-phase AC of 50Hz.It is mainly used for opening and closing the load current, overload current, short circuit current in power...
Product Details

PRODUCTION INTRODUCTION

ZW32 series outdoor high-voltage vacuum circuit breaker(VCB) is used in the three-phase power system with AC 50Hz  as the function of opening and closing load current, overload current and short-circuit current. The VCB is mainly composed of integrated fixed pole, CT, operating mechanism and box. This type of product is miniaturized and equipped with manual emergency opening device. It has the following product structure features:

1.The box shell is made of high-quality stainless steel or ordinary steel plate by antirust treatment process and then spraying ultraviolet resistant varnish. 

2. The insulation part is made of epoxy resin and silicone rubber composite insulation material, with high insulation grade and strong anti pollution ability. There is no transformer oil and sulfur hexafluoride gas in the tank, meeting the requirements of oil-free transformation and environmental protection.

3. The operating mechanism is a spring operating mechanism, with manual and electric modes. The design of unique buffer device, excellent performance, small rebound, low noise.

4. The vacuum interrupter adopts special stainless steel brazing technology, which is stable and reliable with low air leakage rate. Advanced ceramic metallization technology ensures the air tightness of products

5. The CT is made of high-quality magnetic conducting material and composite insulation of epoxy resin and silicone rubber. 

6. According to the user's needs, it can cooperate with the corresponding controller to form auto recloser and sectionalizer, which is the ideal equipment to realize the distribution network automation.


timg (7)


ZW32  installed with intelligent controller,as an Auto Recloser, can realize remote operation and multiple automatic reclosing or permanent fault isolation.It can detect the fault current and automatically open and close in the AC line according to the predetermined sequence, and then reset and lock automatically. The recloser can be opened and closed for many times according to the preset action sequence.The intelligent VCB has the function of small current grounding protection, and the parameters can be continuously adjusted.It can realize the wired remote control and the wireless remote control under the pole.The main functions are as follows:

-Automatic removal of single-phase grounding fault. 

When the single-phase ground fault occurs in the subscriber line, the VCB will automatically open, and other branch lines of the substation and feeder will not be affected by the fault;

-Automatic isolation of phase to phase short circuit fault.

 In case of phase to phase short circuit fault in the subscriber line, the VCB will trip pior to the outlet switch of the substation and automatically isolate the fault line. The power supply of other feeder branches will not be affected by this fault.



QQ图片20191203122224


MODEL DESCRIPTION


1528861921



ADVANTAGES


1.Modular design

2.Compact and lightweight,easily installed on poles or in substations.

3.Maintenance free throughout life.

4.Highly resistant to ozone, oxygen, moisture, contamination and ultraviolet light.

5.Adapt to adverse weather conditions and dirty environment.








20190813093601075





TECHNICAL PARAMETERS OF ZW32-12 



NO.

Item

Unit

 Data

1

Nominal  Voltage

KV

12

2

Rated  Frequency

HZ

50

3

Rated  Current

A

630

4

Rated Short-circuit Breaking Current

KA

20

5

Rated  peak withstand current

KA

50

6

Rated Short-time withstand Current

KA/S

20/4

7

Mechanism life

Times

10000

8

Rated short-circuit closing breaking Number

Times

30

9

Rated operating sequence


O-0.3s-CO-180s-CO

10

Rated breaking current number

Times

10000

11

Rated short-circuit close-open current

KA

50

12

1min Power-frequency 

withstand voltage

Dry

KV

42/48

Wet

KV

34

13

Lighting impulse withstand voltage(Peak Value)

KV

75/85


ENVIRONMENT CONDITION


1. Ambient air temperature: -25°C~+40°C;
2. Altitude: no more than 2000m;
3. The ambient air may be polluted by dust, smoke, corrosive gases, steam or salt fog;
4. The wind speed does not exceed 34m/s;
5. Vibration or ground motion from the switchgear and control equipment is negligible;
6. If beyond the above normal use conditions, pls discuss with the manufacturer.


INSTALLATION AND MAINTENANCE


a. Operators should have a preliminary understanding of product performance, installation and adjustment, and maintenance knowledge. Problems in operation shall be recorded and the manufacturer notified as necessary.

b. Visual inspection shall be conducted for outdoor vacuum circuit breaker before installation. Check whether the insulating sleeve is damaged, whether the opening / closing and storage instructions are leaking, and whether the box is deformed. After inspection, the product shall be installed on the column above 4m. When installing the VCB with disconnector, the accuracy of the mechanical interlocking device shall be carefully checked.

c.The parameters  were adjusted at the time of factory inspection. The user does not have to turn on the machine for inspection. The installation can only be carried out after the pressure test as required.

d. Before the product is put into operation, carefully check whether the rated voltage and current of each operating element are consistent with the actual situation. This mechanism is used to check whether the movement is correct.




INSTALLATION DIAGRAM(single  pole installation)

ZW32 has a variety of installation methods, common is divided into single pole installation and double pole installation.

QQ图片20190909103816

1.ZW32 VCB        2.voltage transforemr      3.controller mounting braket    4.controller

5.telegraph pole  6.cable