ZW32 series outdoor high-voltage vacuum circuit breakers are outdoor high-voltage distribution devices with rated voltage of 12KV-36KV and three-phase AC of 50Hz.It is mainly used for opening and closing the load current, overload current, short circuit current in power...
Product Details
Product Description
The recloser is designed to provide self-contained 24KV circuit protection with series trip,solenoid operation and electronic control single break contact structure and fault interruption under vacuum. The recloser is designed to sense line-to-ground, line-to-line or three-phase fault currents and interrupt all three phases of the distribution circuit simultaneously. The recloser is equipped with a electronic type ground feature. For fault target,Automatic Circuit recloser will be provided with an indicator for detection of fault current on individual phase or ground. If the Electronic Control cubicle of Reclosers or Recloser itself require an auxiliary transformer, the manufacturer must provide the same at his cost. The recloser is provided with in-built auxiliary transformer of required rating to provide power supply to the control panel.
Data
Rated voltage, kV
24 30 ,33,
Max. working voltage, kV
36
Rated current, not less than, A
630A / 1600A
Rated breaking current, not less than, kA
20
Electrical dynamic withstand current, kA
51
Operation times
30000
Heating withstand current (during 3 seconds/this parameter must not be as 1 sec) , not less than, kA
20
Open, close reserve, not less than
- By rated current, Close-Open action
- By breaking current, Close-Open action
30000
25
Breaking own period, not more than, ms
45
Full breaking period, not more than, ms
55
Close own period, not more than, ms
60
Testing voltage of lightning impulse, kV
190
1 min testing voltage by voltage with production frequency, kV
95
Cycle of recloser
O-0.02S-C-0.1S
Usage environment
a. ambient air temperature: + 40 ºC ~ - 40 ºC, daily temperature difference: 25K b. the wind speed is not more than 35m / s c. The protection grade of the case is IP64 d. Consider condensation and precipitation e. The earthquake intensity does not exceed 8 f. The solar radiation intensity does not exceed 1000W / m2 (equivalent to 700pa on the cylinder surface) h. The requirements beyond the technical conditions shall be agreed by the user and the manufacturer.