Disconnector Sf6 Circuit Breaker

Model
Nature of the Manufacturer
Other
Product Category
Vacuum Circuit Breaker
Place of Origin
City, Province
Overview
ZW7-40.5 outdoor high voltage vacuum circuit breaker is outdoor high voltage equipment with AC three-phase 50HZ and rated voltage 40.5kV.
Product Details

Product description

ZW7-40.5kV series outdoor H.V. VCB is an electrical appliance equipment with tri-phase AC 50Hz, rated voltage 40.5kV. It is attached to install spring operation mechanism or electromagnetism operation mechanism, can far control electrically operated opening and closing, also can manually store energy, manually opening and closing.

ZW7-40.5 vacuum circuit breaker is mainly used in outdoor 40.5kV power transformer system for control and protection, which is also suitable for normal operation and short circuit protection in the city, the township power distribution network and the industry and mining enterprise. The overall structure of this product is the porcelain insulator column type. The upper porcelain insulator is loaded with vacuum interrupter internal, while the lower porcelain insulator is the prop porcelain insulator, which is suitable for frequent operation place, and has many characteristics, such as good leak-proof quality, anti-aging, withstand high voltage, incombustible, non explosion, long service life, easy to install and maintain and so on. 


Main technical parameter

No.

Item

Unit

Value

1

Rated voltage

kV

40.5

2

Rated current

A

2500

3

Rated frequency

Hz

50

4

1min power frequency withstand voltage(wet)(dry)phase to phase,phase to earth/fracture

kV

80
95/118

5

Lightning impulse withstand voltage(peak)phase to phase,phase to earth/fracture

kV

185/215

6

Rated short  circuit breaking current

kA

31.5

7

Rated short circuit breaking times

Times

30

8

Rated peak withstand current(peak)

kA

80

9

Rated short-time withstand current/duration

kA/S

31.5/4

10

Rated short circuit making current(peak)

kA

80

11

Resistance of main circuit

μΩ

80

12

Mechanical life

Times

10000


Environmental conditions:

No.

Item

Unit

Value

1

Ambient temperature

Max. Temp.

ºC

+40



Min. Temp.


-25



The Max. Daily Temp. difference


25

2

Altitude

m

≤1000

3

Intensity of solar radiation (outdoor)

W/cm2

0.1

4

Pollution class


V

5

Radial thickness of ice

mm

10

6

Wind velocity/Wind pressure (outdoor)

m/s/Pa

34/700

7

Humidity

The average daily relative humidity

%

≤95



The average monthly relative humidity


≤90