With a rated voltage of 12kV,three phase AC frequency of 50Hz, draw out type vacuum circuit breaker can be a flexiable unit to protect line equipment with short-circuit situation or frequent operations.
Product Details
Product description
VS1 vacuum circuit breakers have been designed for indoor use and air insulated switchboards.
Their switching capacity is sufficient to handle any conditions arising from switching of equipment and system components under normal operating and fault conditions, particularly short-circuits, within the parameters of their technical data. The vacuum circuit-breakers of type VB4, designed in column form, can be supplied both as individual units for fixed installation and mounted on chassis. Vacuum circuit-breakers are characterized by their simple and robust construction. They have a long life expectancy. There is no adverse effect on the vacuum, even from frequent switching of operating and short-circuit currents.
Main technical specifications
NO.
Item
Unit
Data
1
Rated voltage
kV
12
2
Rated short-time power frequency withstand voltage ( 1 min)
kV
42( phase to phase,to earth) / 48( isolating distance)
Rated breaking current of capacitor bank ( C2 grade)
A
single fuse 800,back to back fuse 400
26
Distance between contacts
mm
9±1
27
Contact stroke
mm
3±1
28
Average closing speed
m/ s
0. 5~0. 9
29
Average opening speed
m/ s
1- 1. 7
30
Three - phase contactor opening and closing simultaneity
ms
≤1
31
Contactor closing bounce time
ms
<2
32
Mechanical life(M2 grade)
times
20000
33
Moving and static contactor allows accumulated wear thickness
mm
3
Main characteristics 1) Test voltage according DIN VDE 0670, part 1000, list 2 2) 4000 A with forced cooling 3) 3150 A with forced cooling in AP technology 4) Higher values on request 5) 360 mm for fixed, 280 mm for withdrawable Version 6) Circuit-breaker with heat sink 616 mm 7) Withdrawable Version 8) Circuit-breaker with heat sink 634 mm