ZW32 24 Kv Pole Mounted Vacuum Circuit Breaker is an indoor automatic current reclosers. It can be applied to close and break current , overload current, and short-circuit current in country power net, city power net or other power system.
Product Details
Main Functions:
1) Protective Function - It will identify fault current automatically; realize instantaneous current cutoff, time limited current break, regular flow, directional flow, overvoltage, under-voltage, single phase ground protection of small current ground system, and cooling load start and inhibition of open circuit, and other functions. 2) Measurement Function - Measure three-phase current, three-phase voltage, active power, reactive power, active energy, reactive energy, peak/valley electricity, power factor and frequency etc. 3) Controlling Function - It can realize on-site operation and remote control. Meanwhile, achieve fault location of circuit, fault isolation automatically, resume power supply for the circuit without fault rapidly by requirement; realize automatic load shedding under low frequency, capacitor automatic cutting, automatic cutting of backup power, and other controlling functions. 4) Communication Function - It can report fault, operation and controlling information to appointed personnel through wireless public network or special communication network; support various kinds of communication ways and agreement; realize setting parameters modification by handhold PDA. The controller releases the instruction of self-inspection from PDA and feedback the self-inspection information to PDA terminal. 5) Data Record Function - Record, save and run operation and fault information automatically. 6) Synchronous Switching On/Off Function - According to the features of load, it searches zero crossing point automatically; adapt itself to the discreteness of switch parameter and impact of environment factors; realize synchronous switching on/off; restrain over voltage of operation and inrush phenomenon effectively, especially suitable for switching capacitor and transformer. 7) Intelligence Function - It can carry out on-line comprehensive analysis of power network parameters, on-line performance parameter measurement of circuit breaker, and on-line programming; cooperate with the main station of power distribution automatic system; realize the function of remote control management of switch device, and on-site, remote or hierarchical control type power distribution automation system.
Working Condition
Description
Unit
Using Environment Value
Surrounding Air
Max Temperature
ºC
+50
Min Temperature
-50
Max Daily Temperature Difference
K
30
Altitude
m
≤2,000
Solar Radiation Intensity
W/cm2
0.1
Pollution Class
IV
Icing-Thickness
mm
10
Humidity
Average Value of Daily Relative Humidity
%
≤100
Average Value of Monthly Relative Humidity
≤95
Earthquake Tolerance Ability
Degree
≤8
Remark: please contact us if the environment parameters exceed the range as required in above table.