Recloser For Distribution And Substation

Model
Nature of the Manufacturer
Other
Product Category
Vacuum Circuit Breaker
Place of Origin
City, Province
Overview
ZW32 Outdoor HV column type Vacuum Circuit Breaker is a kind of outdoor distribution equipment.It is mainly used in medium voltage overhead line network as load current, overload current and short circuit current. It is suitable for the rural power network and frequency operation, especially for the urban and rural power network improvement.
Product Details

General

Volcano strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.

The ZW32 series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60HZ power system. and its rated current can reach 1250A.

The ZW32 series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.



QQ图片20191203122224


Main technical data

No.ItemUnitData for ZW32-12KVData for ZW32-15KV
1Rated VoltageKV1215
2Rated insulation level
(phase to ground, phase to phase)
1 min Frequency withstand voltageDryKV4250
Wet3445
Lighting Impulse Withstand Voltage(Peak)KV75110
3Medium Interruption:Vacuum
4Medium isolation:Solid polymer
5Mechanism of operation (closing and shot):Magnetic
6Assembly:Suitable weather for substation
7Environmental operating temperature:FROM -40ºC-+50ºC
8Position indicator: Green-closed; Open-red
9Minimum distance of contouring of the insulationMM400600
10Rated FrequencyHz50/60
11Rated CurrentA630/800/1250
12Rated Min Start-up CurrentNumericalAadjustable
Permissible deviation%±10
13Rated Fault Interrupter CapacityKA/3s12.5/20
14Rated Fault Symmetrical Making CurrentKA12.5/20
15Rated Short-Time Withstand CurrentKA12.5/20
16Rated Peak Withstand CurrentKA12.5/20
17Interrupting Time(Max) (Cycle)sNo more than 4
18The conditions of different phase earthed fault short-circuit breaking currentKA17.3
19Rated Cable Charging Breaking currentA25
20Rated Operating Sequence
O-0.1s-CO-2s-CO-2s-CO-C
21Rated Operation VoltageVAC/DC110/125/220/240
22Rated Short-Circuit Current Breaking TimesTime
90%~99% Rated Short-Circuit Current volume16
45%~55% Rated Short-Circuit Current volume44
15%~20% Rated Short-Circuit Current volume56
23Mechanical Life (Mechanical stability)Time/Unit Operation15000
24Current TransformerPrimary Rated CurrentA600/1000
Secondary Rated Current1 or 5
Accuracy GradeCL0.2/5P20
CapabilityVA15
25Special Manual Closing Mechanism
optional
26Earthing
Solidly Earthed


PRODUCT SCHEMATIC DIAGRAM