The main circuit of the composite insulated cylindrical vacuum circuit breaker adopts a structure in which a vacuum arc extinguishing chamber is sealed in an insulating pole. The vacuum tube is installed longitudinally in a tubular insulation tube. The insulation tube is cast by epoxy resin...
Product Details
product introduction
Vacuum circuit-breakers have particular advantages for use in networks where there is a high switching frequency in the working current range and/ or where a certain number of short- circuit breaking operations are expected. VS1 vacuum circuit- breakers are suitable for auto reclosing and have exceptionally high operating reliability and long life. The circuit- breakers are notable for their compact design, small dimensions together with high capacity. The operating mechanisms have a low maintenance requirement and the interrupters are maintenance- free throughout their service lives. They are well suited to all load breaking operations which occur in practice, and in particular:
Short-circuit currents;
Overhead lines under load and, no-load conditions;
Cables under load and no-load conditions;
Transformers under load and no-load conditions;
Generators under load and no-load conditions;
Ripple control system;
Capacitor banks(also parallel switching) and Motors with starting currents above 600A;
Service environment:
a) Air temperature: Maximum temperature: +40ºC; Minimum temperature:-25ºC b) Humidity: Monthly average humidity 95%; Daily average humidity 90%. c) Altitude above sea level: Maximum installation altitude: 2500m d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
Main technical specifications:
No
Item
Unit
Parameter
1
Rated voltage
kV
12/17.5
24
2
Rated frequency
Hz
50/60
3
Rated current
A
630…4000A
4
1min power frequency withstand voltage
kV
48
65
5
Lightning impulse withstand voltage
kV
75/95
125/150
6
Rated short circuit breaking current(peak)
kA
50/63/80/100
7
Rated active load and close circuit breaking current
A
63
50
8
Rated short breaking current
kA
20…40
9
Rated short circuit making current(peak)
kA
50/63/80/100
10
Rated cable(line) charging breaking current
A
50 and 10
11
Rated capacitor bank switching current
A
400
12
Rated withstand current(peak)
kA
50/63/80/100
13
Short time withstand current(4s)
kA
20…40
14
Mechanism life
times
10000
Note: For short circuit breaking current & rated current is optional by clients.
Why Choose us?
1. Professional manufacturer with our own factory;
2. We have excellent quality products with strict quality control process.
3. Products are produced by ourselves, which ensures high quality and lead time
4. Factory Manufacturing Enterprise Provide with you Competitive Price and superior quality
5. A wide range of low and high voltage insulators
Any questions or your detailed drawings from you are welcome and will be replied in 24 hours.