The vacuum circuit breaker adopts spring energy storage type operating mechanism , which can be operated by electric or manual.It can also be equipped with a permanent magnet actuator with a long service life of 60000 times, which is used in extremely frequent operation places.The vacuum circuit breaker is designed as a re encapsulated structure, which can be used either as a fixed installation unit or as a with draw-able installation unit together with the chassis.The vacuum circuit breaker is manufactured in acco......
Product Details
The vacuum circuit breaker adopts spring energy storage type operating mechanism , which can be operated by electric or manual.It can also be equipped with a permanent magnet actuator with a long service life of 60000 times, which is used in extremely frequent operation places.The vacuum circuit breaker is designed as a re encapsulated structure, which can be used either as a fixed installation unit or as a with draw-able installation unit together with the chassis.The vacuum circuit breaker is manufactured in accordance with the national standard GB1984-2003 and relevant IEC standards.
Application and Attention
1. Guide device must be provided for interrupter during operation. The coaxiality of the moving guide pole and the axis of the arc extinguishing chamber must meet the requirements. Torque on bellows is not allowed.
2. During installation, it is forbidden to knock or impact the interrupter shell with hard objects to avoid air leakage due to cracks.
3. Pay attention to make sure that the conducting pole is coaxial with the interrupter, and that the conducting pole is perpendicular to the end face of the fixed end.
4. Pay attention not to remove the interrupter repeatedly to avoid screw slipping. Do not torque the moving conducting rod, and do not overpressure the bellows, so as to avoid torque force and scratches and reduce the service life of the bellows.
5. During installation, the force applied on the surface of both ends shall not exceed the static pressure relief specified in the specification.
Technical Parameter
Item
Description
Unit
Data
1
Rated voltage
KV
12
2
Max. voltage
KV
12
3
Rated current
A
630/1000/1250
1250/1600
/2000/2500
1250/1600
/2000/3150
4
Rated short circuit opening current
KA
20/25
31.5
40
5
Rated short circuit closing current
KA
50/63
80
100
6
Rated peak withstand current
KA
50/63
80
100
7
4s Rated short-time withstand current
KA
20
31.5
40
8
Rated insulation level
Power frequency
withstandvoltage
KV
42,fracture48
Impulse withstand
voltage(peak)
75,fracture85
9
Rated operating sequence
O-0.3s-C&O-180s-C&O
10
Mechanical life endurance
Times
10000
11
Rated short-circuit opening current sequence
Times
50
12
Clearance between open contacts
mm
11±1
13
Super stroke (the compress length of contact spring)
mm
3.5±0.5
14
Different period among phases for breaking and closing