Welcome Customer !

Membership

Zhejiang Volcano electrical technology Co., Ltd
Free Member ·1YRS
,
Other

Main Products: 断路器

Xwboo>Products

Zhejiang Volcano electrical technology Co., LtdFree·1YRS

  • E-mail

    info@volcano-electrical.com

  • Phone

    +86-577-61668058

  • Address

    Building 2,59, Weishiliu Road, Economic Development Zone, Chengdong Street, Yueqing, Zhejiang, China

Contact Now

12KV Indoor VCB

Model
Nature of the Manufacturer
Other
Product Category
Vacuum Circuit Breaker
Place of Origin
City, Province
Overview
VS1 with rated voltage 12KV, as one type of vacuum circuit breaker, is widely applied to places where frequent operations are needed...
Product Details

VCB stands for Vacuum Circuit Breaker. In VCB, the vacuum is used as the arc quenching media.Nowadays, VCB is widely used in high-voltage substationsor power transmission systems due to the advantages, such as strong interruption capacity, long service life, safety and reliability, and high cost performance.VS1 with rated voltage 12KV, as one type of vacuum circuit breaker, is widely applied to places where frequent operations are needed.According to the different installation forms in switchgear, it can be fixed type or handcart type.Handcart type vacuum circuit breakers are usually suitable for KYN28 series cabinets.The fixed type is applicable to XGN series.

WORKING PRINCIPLE

The VCB consists of fixed contact, moving contact and arc shield mounted inside a vacuum interrupter. The movable member is connected to the control mechanism by stainless steel bellows. This enables the permanent sealing of the vacuum chamber so as to eliminate the possibility of the leak.Under normal operating conditions, these contacts remain closed and will not open automatically until and unless the system becomes faulty.When a fault occurs on any part of the system, the trip coils of the breaker get energized. The moving contacts are pulled apart by some mechanism, thus opening the circuit.

QQ图片20190918133357



TECHNICAL PARAMETERS OF VS1 -12KV INDOOR VCB

Rated voltage

KV

12

Maximum working voltage

KV

12

Rated Current

A

630-1250

1250-2500

1250-3150

Rated short circuit breaking current

KA

20

31.5

40

Rated short-circuit switching current

KA

50

80

100

Rated peak withstand current

KA

50

80

100

4S rated short-circuit withstand current

KA

20

31.5

40

Rated

Insulation

level

Power frequency withstand voltage

KV

42(fracture 48)

Impulse withstand voltage

KV

75(fracture 85)

Rated short-circuit current breaking times

Times

50

Contact opening distance

mm

11±1

Super stroke

mm

3.5±0.5

Closing/Opening Time Difference Among Phases

ms

≤2

Contact closing bounce time

ms

≤2

Average opening speed

m/s

0.9-1.2

Average closing speed

m/s

0.5-0.8

Tripping Time

Maximum operating voltage

s

≤0.05

Minimum operating voltage

s

≤0.08