Welcome Customer !

Membership

Zhejiang Volcano electrical technology Co., Ltd
Free Member ·1YRS
Other

Main Products: 断路器

Xwboo>Products

Zhejiang Volcano electrical technology Co., LtdFree·1YRS

  • E-mail

    info@volcano-electrical.com

  • Phone

    +86-577-61668058

  • Address

    Building 2,59, Weishiliu Road, Economic Development Zone, Chengdong Street, Yueqing, Zhejiang, China

Contact Now

Outdoor Pillar Type Vacuum Circuit Breaker

Model
Nature of the Manufacturer
Other
Product Category
Vacuum Circuit Breaker
Place of Origin
City, Province
Overview
ZW32 series outdoor pillar type vacuum circuit breakers are generally used in three-phase 11kv to 33kV outdoor medium voltage power system. It is suitable for closing and breaking load current, overload current and short-circuit current. Outdoor vacuum circuit breaker can be equipped with reclosing controller to identify current characteristics and realize multiple reclosing or permanent fault isolation.
Product Details

ZW32 series outdoor pillar type vacuum circuit breaker(VCB) is generally used in three-phase 11kv to 33kV outdoor  power system. It can be equipped with reclosing controller to identify current characteristics and realize multiple reclosing or permanent fault isolation.

201807051417173836

PRODUCT CHARACTERISTICS


1.The product adopts a three-phase column structure, with stable and reliable breaking performance, no danger of combustion and explosion, and no need for any maintenance.

2. It adopts totally closed structure design, with good air tightness, which is conducive to improving the moisture-proof  performance, especially suitable for the cold and humid areas.

3. The VCB adopts miniaturized spring operating mechanism, with low power of energy storage motor and low energy consumption of point closing. The transmission adopts the real driving mode, with fewer parts and high reliability.

4. The circuit breaker can be equipped with current transformer(CT), over-current automatic trip protection and information analysis intelligent controller. After being installed with the controller,  power distribution network automation can be realized.
According to customer's requirement, measurement CT can also be installed. The CT adopts imported outdoor solid insulation epoxy resin or indoor outsourcing silicone rubber solid insulation, with high and low temperature resistance, UV resistance, aging resistance, etc.

5. Series drive type isolating switch can be installed for  ZW32 . It has obvious fracture when breaking, and there is anti misoperation interlock device between the VCB bodies.The VCB can only be operated when the isolating switch is completely closed or disconnected.


TECHNICAL PARAMETERS


NO.

Item

Unit

 Data

1

Nominal  Voltage

KV

12

2

Rated  Frequency

HZ

50

3

Rated  Current

A

630

4

Rated Short-circuit Breaking Current

KA

20

5

Rated  peak withstand current

KA

50

6

Rated Short-time withstand Current

KA/S

20/4

7

Mechanism life

Times

10000

8

Rated short-circuit closing breaking Number

Times

30

9

Rated operating sequence


O-0.3s-CO-180s-CO

10

Rated breaking current number

Times

10000

11

Rated short-circuit close-open current

KA

50

12

1min Power-frequency 

withstand voltage

Dry

KV

42/48

Wet

KV

34

13

Lighting impulse withstand voltage(Peak Value)

KV

75/85