Brand Name: MEANRAYPlace of Origin: Zhejiang, ChinaModel Number: MR-PV600Color: REDType: MR-PV600Electricity Type: DC
Product Details
DC SURGE PROTECTIVE DEVICE
MR-600PV
Brand Name: MEANRAY Place of Origin: Zhejiang, China Model Number: MR-PV600 Color: RED Type: MR-PV600 Electricity Type: DC Certificate: IEC,CB,ISO,CE Price: High competitive prices Visual Indication: Green=OK,
Features a.Adopt independent intelligence property right and high performance sensitivity resistance plates b.Small creepage current,fast response time, remnant low voltage c.With remote connection, can realize remote contro d.Module design, convenient installation,with easy electric maintains operation e.Built-in over current and over heat, temperature control open circuit technology
SPECITICATIONO
MR2-PV series surge protector
MR-PV
PV DC-specific
IEC66143-1/EN61643-31
Pole
2P
2P
2P
Electrical parameter
Classified test
Ⅱ
Ⅱ
Ⅱ
UCPV(VDC)
500
600
800
In(8/20)us (kA)
20
20
20
Imax(8/20)us (kA)
40
40
40
Up(kv)
2.8
2.8
3
Remote control and indication
Indication window
Plug-in Module
Remote signal control
Remote signal control
maximum workng voltage(V)
250 AC/30VDC
250 AC/30VDC
250 AC/30VDC
maximum workng current(A)1A(250V/AC)
1A(250V/AC)
1A(250V/AC)
1A(250V/AC)
1A(30VDC)
1A(30V/AC)
1A(30V/AC)
1A(30V/AC)
Wiring & installation
Wiring capacity(mm2)
Hard wire
4~25
4~25
4~25
Flexible wire
4~16
4~16
4~16
Stripping length(mm)
10
10
10
Terminal screwa
M5
M5
M5
Tarque(Nm)
Main cirult
3.5
3.5
3.5
Remate signal contact
0.25
0.25
0.25
Protection class
All profile
IP40
IP40
IP40
Connection port
IP20
IP20
IP20
Installation environment
NO obvious shock and vibration
Altitude(m)
≤2000
≤2000
≤2000
Working Temperatture
-3~+70
-3~+70
-3~+70
Relatlve humiclity
30%~90%
30%~90%
30%~90%
How to install
Installed with H35-7.5/DIN35 steel mounting rall
Size(mm)(W*H*L)
W
36
36
36
H
90
90
90
L
70
70
70
Weight(kg)
0.24
0.24
0.24
DIMENSION
WORKSHOP
EXHIBITION
How to Choose SPD type?
Type 1 SPD
The Type 1 SPD is recommended in the specific case of service-sector and industrial buildings, protected by a lightning protection system or a meshed cage.
It protects electrical installations against direct lightning strokes. It can discharge the back-current from lightning spreading from the earth conductor to the network conductors.
Type 1 SPD is characterized by a 10/350 µs current wave.
Type 2 SPD
The Type 2 SPD is the main protection system for all low voltage electrical installations. Installed in each electrical switchboard, it prevents the spread of overvoltages in the electrical installations and protects the loads.Type 2 SPD is characterized by an 8/20 µs current wave.
Type 3 SPD
These SPDs have a low discharge capacity. They must therefore mandatorily be installed as a supplement to Type 2 SPD and in the vicinity of sensitive loads.
Type 3 SPD is characterized by a combination of voltage waves (1.2/50 μs) and current waves (8/20 μs).