How to control the motor speed of the inverter
1. Why can the rotation speed of the motor change freely?
Motor rotation speed unit: R/min rotate the number of times per minute, or it can also be expressed as RPM.
For example: 2 pole motor 50Hz 3000 [R/min]
4 Polar Motors 50Hz 1500 [R/MIN]
Conclusion: The rotation speed of the motor is proportional to the same frequency
The rotation speed of the inductive AC motor (referred to as a motor in the future) is similar to the extreme and frequency of the motor. The working principle of the motor determines that the motor is constantly fixed. Because the extreme value is not a continuous value (a multiple of 2, for example, the maximum number is 2,4, 6), the speed of the motor is generally unsuitable and changes the value by changing the value.
In addition, the frequency can be adjusted outside the motor before providing the motor, so that the rotation speed of the motor can be freely controlled.
Therefore, the frequency converter for the purpose of controlling the frequency is a preferred equipment for motor speed regulating equipment.
n = 60F/P
N: Synchronous speed
F: Power frequency
P: Electric pole pair
Conclusion: Change the frequency and voltage is the optimal motor control method
If the frequency is only changed and the voltage is not changed, the motor will cause the motor to be burned out when the frequency is reduced, resulting in the motor may be burned out. Therefore, the inverter must change the voltage at the same time while changing the frequency. When the output frequency is above the rated frequency, the voltage cannot continue to increase. The maximum can only be equal to the rated voltage of the motor.
For example: In order to minimize the rotation speed of the motor, the output frequency of the inverter is changed from 50Hz to 25Hz. At this time, the output voltage of the inverter needs to be changed from 400V to about 200V
2. What about the output torque when the rotation speed (frequency) of the motor changes?
The starting torque and maximum torque of the frequency conversion is less than the direct use of the operating frequency power supply.
The motor starts and accelerates a large impact when power supply power supply, and these shocks are weaker when using inverters. The direct start of the work frequency will generate a large starting current. When using the inverter, the output voltage and frequency of the inverter are gradually added to the motor, so the motor's current and impact are smaller.
Generally, the torque generated by the motor must be reduced with the frequency (decrease). The reduced actual data will be given in some inverter manuals.
By using a magnetic flux vector control inverter, the lack of torque at low speed of the motor will be improved, and even the motor in the low -speed area can output sufficient torque.
3. When the frequency frequency adjustment to the frequency of 50Hz, the output torque of the motor will be reduced
The usual motor is designed and manufactured at 50Hz voltage, and its rated torque is also given within this voltage range. Therefore, the speed regulation under the rated frequency is called constant torque speed regulation. (T = Te, P)
When the output frequency of the inverter is greater than the 50Hz frequency, the torque generated by the motor decreases the linear relationship with the frequency of the frequency.
When the motor is running at a frequency speed of 50Hz, the size of the motor load must be considered to prevent the motor's lack of torque.
Example: The torque generated by the motor at 100Hz should be reduced to 1/2 of the torque when 50Hz.
Therefore, the speed regulation above the rated frequency is called constant power speed regulation. (P = UE*IE)
4. Application of inverter 50Hz or above
Everyone knows that for a specific motor, its rated voltage and rated current are unchanged. For example, the rated values of the frequency and motor are: 15kW/380V/30A, and the motor can work above 50Hz.
When the speed is 50Hz, the output voltage of the inverter is 380V and the current is 30A. At this time, if the output frequency is increased to 60Hz, the maximum output voltage current of the inverter can only be 380V/30A, which is obviously the output power unchanged. Therefore, we call it constant power speed adjustment.
What is the torque at this time? Because P = WT (W: angle speed, t: torque). Because P is unchanged and W has increased, the torque will be reduced accordingly.
We can also look at it from another angle: the stator voltage of the motor u = E + I*R (i is current, R is an electronic resistor, E is an inductive potential) can be seen that when U and I remain unchanged, E is not e none Change. E = k*f*x, (k: constant, f: frequency, x: magnetic flux), so when f consists of 50 -> 60Hz, x will be reduced accordingly
For the motor, t = k*i*x (k: constant, I: current, x: magnetic flux), so torque T will decrease with magnetic flux X. At the same time, when it is less than 50Hz, because I*R is very small, when U/F = E/F remain unchanged, the magnetic flux (x) is the constant, and the torque T is proportional to the current. This is why it is usually described by the transient power of the inverter to describe its overload (torque) ability. It is also called constant torque speed adjustment (the rated current is unchanged-> the maximum torque is unchanged)
Conclusion: When the output frequency of the inverter increases from more than 50Hz, the output torque of the motor decreases.
5. Other factors related to the output torque
Heating and heat dissipation capabilities determine the output current capacity of the frequency frequency, which affects the output torque capacity of the inverter.
Carrier frequency: The rated current marked by the general inverter is at the highest carrier frequency. The maximum ambient temperature can ensure the continuous output value. Reduce the carrier frequency. The current of the motor will not be affected, but the heating of the component will decrease.
Environmental temperature: It does not increase the current value of the inverter because it is not detected when the surrounding temperature is relatively low.
Altitude: The height of altitude increases, which has an impact on both heat dissipation and insulation performance. Generally, it can be considered without considering 1000m. The above 1000 meters can be reduced by 5%.