How to use the frequency converter to realize deceleration and stop if the motor has no holding brake? ★It is completely possible to use the braking unit of the inverter's internal structure to decelerate and stop, but it is necessary to learn the function code settings of the inverter. The current inverters all use braking resistors to decelerate and stop. According to different powers, braking resistors with different resistance values are selected and connected to the + and PB terminals of the inverter to perform deceleration braking and stopping. However, it depends on the instruction manual of the specific inverter. Because the function codes set by different inverters are different, at this time, the "free stop" must be turned off and the deceleration stop function must be turned on, including the deceleration time, the setting of the initial frequency range of DC braking at stop, That is to say, after receiving the stop command at the normal operating frequency, the inverter will automatically operate for a period of time, and the braking resistor will be discharged to remove the electric energy required for the motor to run, so as to achieve the purpose of braking.



★The setting of DC braking function. ①DC braking function before starting; since the inverter has preset the starting frequency, the motor starts from the lowest speed. If the motor has a certain speed when starting, the inverter will trip due to overcurrent or overvoltage. In addition, with loads such as blowers, the blades will rotate in the opposite direction on their own under the action of the wind, even in a shutdown state. At this time, when the motor is started, an overcurrent will be generated.


In order to avoid the above situation, some inverters set the DC braking function before starting to ensure that the motor starts from zero speed when the motor is completely stopped.


(The load machine with large inertia of the DC braking function often fails to stop, that is, there is a phenomenon of "creep" (or crawling) after the shutdown, which may cause serious consequences to the transmission equipment or production process. For this reason, the frequency conversion The DC braking function is set in the controller to overcome the occurrence of this phenomenon. During DC braking, a DC current is passed into the stator winding of the motor, so that the asynchronous motor is in a state of energy consumption braking, and the motor stops quickly.



The DC braking function mainly sets the following three parameters. a. DC braking starting frequency fDB. In most cases, DC braking is used in conjunction with regenerative braking. First use regenerative braking to reduce the motor speed to a lower value, and then convert to DC braking to stop the motor quickly. The turning frequency of the motor from regenerative braking to DC braking is the starting frequency fDB of DC braking.


The size of fDB is mainly set according to the requirement of the negative number for the braking time. The shorter the braking time required, the larger the starting frequency fDB should be. b. DC braking amount. The DC braking amount is the size of the DC voltage UDB applied to the stator winding of the motor. The larger the UDB, the greater the braking torque generated, and the faster the motor stops. When setting, the size of UDB should be slowly set from small, mainly according to the size of load inertia. The larger the load inertia, the larger the set value of UDB.


c. DC braking time tDB. The length of time that the DC voltage UDB is applied is called the DC braking time.



The size of tDB is mainly set according to the severity of the load "creep" (creep). For those with higher requirements to overcome "creep", tDB should be appropriately larger so that there is enough DC current to brake. But the DC braking current should not exceed the rated current of the inverter.