How to adjust the soft start control cabinet after installation
First, pay attention before installing the soft starter in the soft start control cabinet. You should first check whether the soft starter is damaged during transportation, and whether the nameplate meets your own requirements.
Second, the soft start control cabinet should be carefully checked after the installation is completed. Check whether the wiring is correct and whether the connection is reliable according to the design drawings. Electronic devices such as thyristors are not allowed to do insulation resistance tests. Only the high resistance gear of a digital multimeter can be used to check the insulation of the thyristors in the soft starter.
3. The measured resistance value between the input and output terminals of each group of thyristors of the new soft starter (in cold state) should indicate about 1.3MΩ, and the measured resistance value between phases (when the control loop is not connected between phases) and relative measured resistance value should indicate infinity.
Fourth, after checking and confirming that it is correct, connect a small power motor to the output end of the soft starter and set the technical parameters such as starting mode, initial voltage, starting time and stopping time. Before connecting the motor to the soft starter, the motor and cable insulation must be checked with a 500V insulation resistance tester. Only when the insulation resistance complies with the relevant regulations, the motor is allowed to be connected to the output terminal of the soft starter for the start-up test.
Fifth, before the first soft start, the machine should be manually turned to check whether the machine is "jammed". Then, after the equipment start-up test and the start-up parameters are adjusted, it can be delivered for use.
In short, the soft starter has a large starting torque and can be adjusted, the equipment starting time is short, it has a soft stop function, and there are few components and a small maintenance amount.
Last Article: What is the soft start of three-phase asynchronous motor