How to calculate the heat generated by the frequency converter and the required ventilation
Variable frequency drives are commonly used to control motor speed in applications such as fans, pumps, compressors, elevators, extruders, and more.
Heat loss of the inverter
The amount of power delivered to the motor through the variable frequency drive is lost as heat. The heat loss of the drive can be expressed as
loss = P t (1 - η d) (1) where H loss = heat loss in the variable frequency drive environment (kW) P t = electrical power through the variable frequency drive (kW) η d = variable frequency drive efficiency
Heat loss in imperial units
loss = P t 3412 (1 - η d) (1b) where H loss = variable frequency drive environment heat loss (btu/h) P t = inverter power (kW) η d = variable frequency drive efficiency
To calculate the maximum heat loss - the maximum power transfer through the frequency converter must be used.
It is common that the heat loss from the frequency drive is in the range 2 - 6% of the KVA rating.
Necessary ventilation for cooling the frequency converter
The maximum ambient temperature for the drive is approximately 40 o C (104 o F). Since drives are often physically protected in small cabinets or small rooms, ventilation - or even cooling - may be required to avoid overheating.
The mass air flow required to transfer heat from a variable frequency drive can be expressed as
m air = H loss / c p (t out - t in) (2) where m air = air mass flow (kg/s) H loss = heat loss from frequency driven environment (W) c p = specific heat air (kJ/kg) o C) (1.005 kJ/kg o C standard air) t out = outlet air temperature (o C) t in = air temperature in (o C)
Combined with (1), the mass flow (2) can be expressed as:
m air = P t(1 - η d)/C p(t out - t in) (2b)
Volume flow can be calculated by multiplying (2b) by a specific volume or inverse density:
q air = (1/ρ air) P t (1 - η d) / C p (T out - t in) (2c) where ρ air = density of air at actual temperature (1.205 kg/m3 standard air)
Example - Ventilation and cooling of a frequency converter
The amount of air used to cool the cabinet-mounted drive with a maximum power of 100 kW, an efficiency of 0.95, a maximum ambient operating temperature of 40 o C and an outdoor temperature of 20 o C can be expressed as (2b):
m air = (100 kW) (1 - 0.95 ) / (1.005 kJ/kg. C) ((40 C) - (20 C)) = 0.25 kg/sec
The volume and density of air depend on the temperature of the air. The air density at 20 is 1.205 kg/m3 and 1.127 kg/m3 at 40.
Volume flow at inlet (20 o C):
q air = (1/(1.205 kg/m3)) (0.25 kg/s) = 0.208 m3/s = 749 m3/hour
Volume flow at outlet (40 o C):
q air = (1/(1.127 kg/m3)) (0.25 kg/s) = 0.222 m3/s = 799 m3/hour