How to switch between soft starter and bypass control?
Date: 2022/11/3Read: 34

How to switch between soft starter and bypass control?

Oct 19, 2021

How to switch between soft starter and bypass control?

After the soft starter is started, cut off its own power first, and then start the bypass? Or when the soft start is working, turn on the bypass, and then cut off the soft start itself after the bypass is turned on?


What is the firing angle of the thyristor of our soft starter?


Answer: After the soft start is completed, the bypass contactor will be triggered to close by an internal signal, so that the main circuit current is bypassed from the thyristor to the bypass contactor circuit.


Bypass contactors can be divided into built-in and external, and their switching methods are also different.

The previous old models are mostly external bypass contactors, so the external bypass contact of the soft starter needs to be used to trigger the action of the external bypass contactor coil, that is, when the start is completed, the bypass contact will be Normally open becomes normally closed. At this time, the bypass contactor will be closed, and the main circuit will be switched to power frequency.

At present, the mainstream soft starters are mostly built-in bypass contactors, so when the start-up is completed, the soft starter directly triggers the built-in bypass contactor through an internal signal to turn off the thyristor, and the customer does not need external control. However, if a special design (such as one tow multiple, etc.) is required, the external bypass contactor must be triggered by the signal contact.

Taking the first motor as an example, the soft start working process is as follows: Press the start button S11, the soft start K8 is energized and closed when there is no Alarm, so the K8 normally open point is closed, K20, K30 are not started (or Has been started) Normally closed without action, the start contactor K10 (delay open contactor) of the first motor is energized, the K10 normally open point is closed, the main contactor K1 is also energized and closed, and the first motor is soft-started. When the motor starts, after the motor starts, K9 is closed, and K12 is obtained from the holding power closed. After the delay of K10 is reached, it is disconnected, and K1 is also disconnected. The soft starter quits working and no longer supplies power. You can start the second or third motor by soft start. In this way, the soft start can start a single motor each time without affecting other motors.

For a one-to-one soft starter, after starting the motor, the side contactor closes and works, and the soft starter exits the power supply after a short delay. Of course, if it is only one for one, as long as the power of the soft starter is not less than the power of the motor, there is no problem without the bypass contactor.