How to debug the inverter
The following steps should be done first:
1. No-load power-on inspection of the inverter
1 Ground the ground terminal of the inverter.
2 Connect the power input terminal of the inverter to the power supply through the leakage protection switch.
3 Check whether the factory display of the inverter display window is normal. If it is not correct, reset it, otherwise it is required to return.
4 Familiar with the operation keys of the inverter. General inverters have 6 keys such as run (RUN), stop (STOP), programming (PROG), data P confirmation (DATAPENTER), increase (UP, ▲), decrease (DOWN, "), etc., different inverter operations The definitions of the keys are basically the same. In addition, some inverters have function keys such as monitor (MONITORPDISPLAY), reset (RESET), inching (JOG), and shift (SHIFT).
2. No-load operation of inverter with motor
1. To set the power and number of poles of the motor, consider the working current of the inverter.
2. Set the maximum output frequency, base frequency, and torque characteristics of the inverter. General inverters are equipped with multiple VPf curves for users to choose, and users should choose the appropriate VPf curve according to the nature of the load. If it is a fan and pump load, the torque operation code of the inverter should be set to variable torque and reduced torque operation characteristics. In order to improve the low-speed performance of the inverter when starting, so that the torque output by the motor can meet the starting requirements of the production load, the starting torque must be adjusted. In the variable frequency speed regulation system of asynchronous motor, the torque control is more complicated. In the low frequency band, the influence of resistance and leakage reactance cannot be ignored. If VPf is kept constant, the magnetic flux will be reduced, thereby reducing the output torque of the motor. For this reason, the voltage should be properly compensated in the low frequency band to increase the torque. Generally, the inverter is manually set and compensated by the user.
3. Set the inverter to its own keyboard operation mode, press the run key and stop key, and observe whether the motor can start and stop normally. .
4. Familiar with the protection code when the inverter is running and fail, observe the factory value of the thermal protection relay, observe the set value of the overload protection, and modify it if necessary. The user of the inverter can set the electronic thermal relay function of the inverter according to the instruction manual of the inverter. When the output current of the inverter exceeds its allowable current, the inverter's overcurrent protection will cut off the inverter's output. Therefore, the maximum threshold value of the electronic thermal relay of the inverter does not exceed the maximum allowable output current of the inverter.
3. Test run with load
1. Manually operate the run stop button on the panel of the inverter, observe the motor running and stopping process and the display window of the inverter to see if there is any abnormality.
2. If the inverter has an overcurrent protection action during starting/stopping the motor, reset the acceleration/deceleration time. The acceleration of the motor during acceleration and deceleration depends on the acceleration torque, and the frequency change rate of the inverter during the startup and braking process is set by the user. If the moment of inertia of the motor or the load of the motor changes, the acceleration torque may be insufficient when the speed is increased or decelerated according to the preset frequency change rate, which may cause the motor to stall. Current or overvoltage. Therefore, it is necessary to set the acceleration and deceleration time reasonably according to the motor's moment of inertia and load, so that the frequency change rate of the inverter can be coordinated with the change rate of the motor speed. The method to check whether this setting is reasonable is to first select the acceleration and deceleration time according to experience and set it. Properly extend the deceleration time. On the other hand, the acceleration and deceleration time should not be set too long, too long will affect the production efficiency, especially when frequently starting and braking.
3. If the inverter still protects within the limited time, the start/stop operating curve should be changed from straight to S-shaped, U-shaped line or S-shaped, reverse U-shaped line. When the motor load inertia is large, a longer start and stop time should be used, and the type of running curve should be set according to its load characteristics.
4. If the inverter still has a running fault, try to increase the protection value of the maximum current, but the protection cannot be cancelled, and a protection margin of at least 10% to 20% should be left.
5. If the inverter operation failure still occurs, replace the inverter with a higher level of power.
6. If the inverter drives the motor to fail to reach the preset speed during startup, there may be two situations:
(1) Electromechanical resonance occurs in the system, and it can be judged from the sound of the motor running. The method of setting the frequency jump value can avoid the resonance point. Generally, the inverter can set three-level jump points. When the inverter controlled by VPf drives an asynchronous motor, the current and speed of the motor will oscillate in certain frequency ranges. In severe cases, the system cannot run, and even overcurrent protection occurs during acceleration, which prevents the motor from starting normally. Or it is more serious when the moment of inertia is small. Ordinary inverters are equipped with frequency jump function. Users can set the jump point and jump width on the VPf curve according to the frequency point where the system oscillates. When the motor accelerates, these frequency bands can be automatically skipped to ensure that the system can operate normally (2) The torque output capacity of the motor is not enough, and the factory parameter settings of different brands of inverters are different. The load capacity of the motor may be different due to different inverter control methods; or the load capacity will be different due to the different output efficiency of the system. In this case, you can increase the value of the torque boost. If it cannot be achieved, the manual torque boost function can be used. Don't set too large, the temperature rise of the motor will increase at this time. If it still does not work, you should switch to a new control method. For example, Hitachi inverters use a constant VPf ratio method. When the startup fails to meet the requirements, switch to a speed sensorless space vector control method, which has a greater torque output capacity. For loads such as fans and pumps, the value of the torque reduction curve should be reduced.
Fourth, the inverter is connected to the host computer for system debugging. After the basic manual setting is completed, if there is a host computer in the system, connect the control line of the inverter directly to the host computer control line, and change the operation mode of the inverter to Terminal control. According to the needs of the host computer system, set the range of the frequency converter receiving frequency signal terminal to 0~5V or 0~10V, and the response speed of the frequency converter to the analog frequency signal sampling. If you need another monitoring meter, you should select the analog output monitoring value, and adjust the range of the inverter output monitoring value terminal.
Inverter no-load debugging method
The commissioning of the variable frequency speed control system should generally follow the rule of "first no-load commissioning, then load commissioning".