How to realize multi-speed control of frequency converter
The realization of the multi-speed operation of the motor through the frequency converter is very widely used in the actual industrial field. Through different switch combinations, different operating frequencies can be set to achieve different operating speeds of the motor. #Inverter#
Today we take the Delta VFD-M series inverter as an example to achieve multi-speed control of the motor operation. Next, let's take a look at what we should do!
1. Control circuit
The figure shows the multi-speed physical connection diagram of the inverter, where the forward rotation start-stop control signal M1 of the M0 inverter is the reverse start-stop control signal of the inverter, and M3, M4, M5 are the multi-speed combination terminals of the inverter. , 7 different operating frequencies can be combined through these 3 terminals.
Figure 2 shows the wiring diagram of the inverter's multi-speed circuit. The M2 multi-function terminal can be set as a fault abnormal reset button, which is empty and not used here.
Note: If the single-phase power is used, any two terminals of the power supply terminal R, S, T can be used as the input power terminal
2. Multi-speed frequency setting table
8 kinds of relationships can be combined through 3 DI terminals, and a frequency can be set for each relationship. The settings are shown in Table 1.
Note: In the table, the "0" in the S3, S4, and S5 switches represents the switch OFF state, and "1" represents the switch closed ON state. In addition, the frequency of each segment can also be set at will.
3. Parameter setting
Normal If you are using an inverter that has been used by others, it is recommended to restore the inverter to its factory settings, and use external terminal control to achieve multi-speed operation when the inverter parameter settings are shown in Table 2.
4. Functional operation instructions
Forward/Stop: When the button S1 is turned on, the motor rotates forward, when the button S1 is turned off, the motor stops
Reverse/Stop: When the button S2 is turned on, the motor reverses, and when the button S2 is turned off, the motor stops
When the motor is running, adjust the frequency setting knob to increase or decrease the main operating frequency.
When only S3 is pressed, it runs at a frequency of 10HZ;
When only S4 is pressed, it runs at 20HZ frequency;
When only S5 is pressed, it runs at a frequency of 30HZ;
When S3 and S4 are pressed at the same time, it runs at 35HZ frequency;
When S3 and S5 are pressed at the same time, it runs at a frequency of 40HZ;
When S4 and S5 are pressed at the same time, it runs at a frequency of 50HZ;
When S3, S4, S5 are pressed at the same time, it will run at 25HZ frequency;
When S3, S4, S5 are not pressed, it runs at 0HZ frequency;